X20AI4322
The module is equipped with 4 inputs with 12-bit digital converter resolution. It is possible to select between the two current ranges 0 to 20 mA and 4 to 20 mA.
I/O module | 4 analog inputs 0 to 20 mA / 4 to 20 mA |
B&R ID code | 0xCAB3 |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Inputs | Yes, using LED status indicator and software |
Power consumption | |
Bus | 0.01 W |
Internal I/O | 1.1 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL | cULus E115267 Industrial control equipment |
HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
EAC | Yes |
Input | 0 to 20 mA / 4 to 20 mA |
Input type | Differential input |
Digital converter resolution | 12-bit |
Conversion time | 400 μs for all inputs |
Output format | |
Data type | INT |
Current | 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA |
Load | <400 Ω |
Input protection | Protection against wiring with supply voltage |
Permissible input signal | Max. ±50 mA |
Output of digital value during overload | Configurable |
Conversion procedure | SAR |
Input filter | Third-order low-pass filter / Cutoff frequency 1 kHz |
Max. error | |
Gain | |
0 to 20 mA | 0.08% |
4 to 20 mA | 0.1% |
Offset | |
0 to 20 mA | 0.03% |
4 to 20 mA | 0.16% |
Max. gain drift | |
0 to 20 mA | 0.009%/°C |
4 to 20 mA | 0.0113% / °C |
Max. offset drift | |
0 to 20 mA | 0.004%/°C |
4 to 20 mA | 0.005 %/°C |
Common-mode rejection | |
DC | 70 dB |
50 Hz | 70 dB |
Common-mode range | ±12 V |
Crosstalk between channels | -70 dB |
Nonlinearity | <0.05% |
Insulation voltage between channel and bus | 500 Veff |
Electrical isolation | Channel isolated from bus Channel not isolated from channel |
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2mm |