X20AO4622
X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution
B&R ID code | 0x1BA3 |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Channel type | Yes, using software |
Power consumption | |
Bus | 0.01 W |
Internal I/O | 1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0) |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL | cULus E115267 Industrial control equipment |
HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
EAC | Yes |
KC | Yes |
Output | ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals |
Max. output current | 10 mA at voltage >5 V 15 mA at voltage <5 V |
Digital converter resolution | |
Voltage | ±12-bit |
Current | 12-bit |
Conversion time | 300 µs for all outputs |
Settling time on output change over entire range | 500 µs |
Switch on/off behavior | Internal enable relay for startup |
Max. error | |
Voltage | |
Gain | 0.08% |
Offset | 0.05% |
Current | |
Gain | 0.09% |
Offset | 0.05% |
Output protection | Short-circuit proof |
Output format | |
Voltage | INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV |
Current | INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA |
Load per channel | |
Voltage | Max. ±10 mA, load ≥1 kΩ |
Current | Load max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0) |
Short-circuit proof | Current limiting ±40 mA |
Output filter | First-order low-pass filter / cutoff frequency 10 kHz |
Max. gain drift | |
Voltage | 0.015%/°C |
Current | 0.02 %/°C |
Max. offset drift | |
Voltage | 0.032%/°C |
Current | 0.032%/°C |
Error caused by load change | |
Voltage | Max. 0.11%, from 10 MΩ → 1 kΩ, resistive |
Current | Max. 0.5%, from 1 Ω → 600 Ω, resistive |
Nonlinearity | <0.007% |
Insulation voltage between channel and bus | 500 Veff |
Electrical isolation | Channel isolated from bus Channel not isolated from channel |
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0) |
Vertical mounting orientation | -25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0) |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2mm |