Specifications
Place of Origin :
china
Price :
Negotiable
Delivery Time :
7-15work days
Payment Terms :
Payment Terms: L/C, T/T, D/A, D/P
Description

General Description:

Hai Bang 12kV Vacuum Contactor-Fuse Combination unit – HCR-12J(D)Y/D200-50T are applicable on AC 50-60Hz power systems, rated voltage 12kV, rated current 200A. HCR-7.2J(D)Y/D315-50T is another type of Vacuum Contactor-Fuse Combination unit, of which the rated voltage is 7.2kV and rated current is 315A.

The Vacuum Contactor-Fuse Combination unit can be installed in the switch cabinet to form an F-C circuit and used in conjunction with a comprehensive protector. The Vacuum Contactor Unit combines a high-voltage fuse capable of breaking a wide range of short-circuit fault currents with a vacuum contactor that can be frequently operated. It can be used for frequent starting of motors and frequent switching of transformers and capacitors.

Vacuum Contactor-Fuse Combination unit is widely used in power systems such as power plants, chemicals, coal mines, metallurgy, ports and wharfs. It can be used by power plants and industrial and mining enterprises to switch on and off AC high-voltage motors, transformers, induction furnaces and other loads, and has the function of short-circuit protection. The trolley at the bottom of the 12kV Vacuum Contactor-Fuse Combination unit can be easily moved out of the control cabinet. The altitude of the environment where the product is used does not exceed 1000 meters above sea level.

Technical Data:

Name

Unit Value

Main circuit

Rated working voltage (Ue)

kV

7.2 12
Rated working current (Ie)(Depends on the fuse)

A

≤315 ≤200
Rated frequency (fr) Hz 50~60
Rated expected short-circuit breaking current (effective value) kA ≤50
Rated expected short-circuit making current (peak value) kA 125
Power frequency withstand voltage

Wiring terminal to earth

kV

32

42

Vacuum breaks

kV

32 42
Lightening impulse withstand voltage

kV

60 75

Control circuit

Rated voltage (Us)

V

AC 110/220/380
DC 110/220
Rated power (Ps)electric holding VA ≤1000/100 (absorbing/holding)
Rated power (Ps) mechanical holding VA ≤900/600 (Closing/opening)

Auxiliary circuit

Form (6a+6b)

Rated value

AC 380V/5A

Control circuit, auxiliary circuit to earth power frequency withstand voltage

kV 2

Rated operating frequency

Long-term

time/h

300

Short-term

time/h 600

Mechanical endurance

10000 times 30

Electrical endurance

10000 times 10(AC-3)

Mechanical characteristics

Closing time

ms

≤150
3-phase asynchronous time ms ≤3
Original opening time ms ≤150(electric holding), ≤60(mechanical holding)
Closing tripping ms ≤4

Remark:

1. Rated control voltage can be made according to customer’s requirements.

2. For the mechanical holding type, the locking device needs to be replaced every 100,000 times.

Hot Tags: 12kv vacuum contactor-fuse combination unit, China, suppliers, manufacturers, factory, 40.5kV Vacuum Contactor, Medium Voltage Vacuum Contactor, Vacuum Contactor 1140V, 12kV Vacuum Contactor-Fuse Combination, 7.2kV Vacuum Contactor Horizontal, 12kV Vacuum Contactor Horizontal

Send your message to this supplier
Send Now

12kV 50Hz / 60Hz 3 Phase Vacuum Contactor-Fuse Combination Unit High Voltage

Ask Latest Price
Place of Origin :
china
Price :
Negotiable
Delivery Time :
7-15work days
Payment Terms :
Payment Terms: L/C, T/T, D/A, D/P
Contact Supplier
12kV 50Hz / 60Hz 3 Phase Vacuum Contactor-Fuse Combination Unit High Voltage

Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd

Verified Supplier
2 Years
jiangsu, wuxi
Since 2011
Business Type :
Manufacturer
Total Annual :
20000000-50000000
Employee Number :
100~150
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement