Hai Bang Plateau type Single Phase Vacuum Contactor is dedicated for plateau environment. It is suitable for power systems with AC 50~60Hz, main circuit rated voltage 7.2kV, 12kV, and rated current 160A~1250A. Plateau type Single Phase Vacuum Contactor is mainly used as a grounding switch when a single-phase ground fault occurs. JCZ1 Plateau type Single Phase Vacuum Contactors are used in arc suppression cabinets and electrical occasions that require single-phase control. The altitude of the environment where the Plateau vacuum contactor is used does not exceed 5000 meters above sea level.
Types:
JCZ1- TG/D160~1250A-7.2kV
JCZ1- TG/D160~1250A-12kV
Application Condition:
1. Ambient Air Temperature: -25℃~+40℃,24-hour average must NOT exceed +35℃;
2. Altitude: 5000m or Lower; We have applied the patent that shows the JCZ1 plateau type vacuum contactor can operate safely and stably within the altitude of 5000m above sea level.
3. Relative Humidity: Daily average less than 95%, Monthly average less than 90%, Must NOT exceed 50% when Ambient Air Temperature reaches +40℃;
4. Operation Environment: Ambient air shall not be contaminated by corrosive, flammable or explosive gas and water vapor, Contamination Level: Level III;
5. Installation of Plateau type high voltage vacuum contactor:
When operating, the tilt angle between the surface of installed Plateau type Single Phase Vacuum Contactor and the horizontal plane shall NOT exceed 5°.
Note: In case the above conditions cannot meet the user's requirements, the user can negotiate with the manufacturer for special treatment of the product.
Technical Data:
Name |
Unit |
Value | |||
Main circuit |
Rated working voltage (Ue) |
kV |
7.2 |
12 |
|
Rated working current (Ie) |
A |
160~1250 | |||
Rated frequency (fr) |
Hz |
50~60 | |||
Rated connecting capacity |
A |
10Ie (AC-2) | |||
Rated breaking capacity |
A |
8Ie (AC-2) | |||
Rated short time withstand current |
A |
10Ie | |||
Rated peak withstand current |
A |
25Ie | |||
Rated short circuit duration |
s |
4 | |||
Ultimate breaking capacity |
A/time |
2500/4, 4000/4, 6300/4, 8000/4 | |||
Power frequency withstand voltage |
Wiring terminal to earth |
kV |
32 |
42 |
|
Vacuum breaks |
kV |
32 |
42 | ||
Lightening impulse withstand voltage |
kV |
60 |
75 | ||
Control circuit |
Rated voltage (Us) |
V |
AC 110/220/380 |
||
DC 110/220 | |||||
Rated power (Ps)electric holding |
VA |
≤1000/100 (absorbing/holding) | |||
Auxiliary circuit |
Form |
4a+3b |
|||
Rated value | AC 380V/5A | ||||
DC 380V/1A | |||||
Control circuit, auxiliary circuit to earth power frequency withstand voltage |
kV |
2 | |||
Rated operating frequency |
Long-term |
time/h |
300 |
||
Short-term |
time/h |
600 | |||
Mechanical endurance |
10000 times |
100 | |||
Electrical endurance |
10000 times |
25(AC-3), 10(AC-4) | |||
Mechanical characteristics |
Closing time |
ms |
≤160 |
||
Original opening time |
ms |
≤100(electric holding) | |||
Closing tripping |
ms |
≤5 | |||
Remark: Rated control voltage can be made according to customer’s requirements. |