TP48-3-N-NDI MTL Instruments TP48 Series Surge Protection
MTL TP48 range
Safeguards electronic process transmitters against induced surges and transients from field cabling
• Protects 2, 3 and 4 wire transmitters
• Easy and direct mounting — screws into spare conduit entry
• Intrinsically safe and flameproof to CENELEC standards
• Parallel connection avoids introduction of any resistance into loop
• ATEX approved
SPECIFICATION
• Maximum surge current
20kA peak current (8/20µs waveform)
• Leakage current
Less than 10µA at max. working
voltage
• Working voltage
35V dc maximum
• Bandwidth
1MHz
• Resistance
No resistance introduced into loop
• Ambient temperature limits
-40°C to +85°C
(-40°F to +185°F) (working)
-40°C to +85°C
(-40°F to +185°F) (storage)
• Humidity
5% to 95% RH (non-condensing)
• Casing
316 stainless steel suitable for harsh environments
• Threads
1/2” NPT
• EMC compliance
To Generic Immunity Standards
BS EN 61326-1:2013 for industrial environments
• Electrical Safety
To BS EN 61643-21:2001 for surge protection devices
Related Models:
HCU16 | MTL5521 | MTL4544 |
HCU3700 | MTL5522 | MTL4544D |
HM64RIB20-1.0 | MTL5531 | MTL4546Y |
HM64RIB20-1.5 | MTL5532 | MTL4549Y |
HMM64 | MTL5541 | MTL4573 |
HMRIB16-1.0 | MTL5541S | MTL4575 |
HMS64 | MTL5544 | MTL4646Y |
HTP-SC32 | MTL5544D | MTL4850 |
MTL4044D | MTL5546 | MTL4851 |
MTL4511 | MTL5546Y | MTL4852 |
MTL4516 | MTL5561 | MTL5018 |
MTL4516C | MTL5573 | MTL5032 |
MTL4521 | MTL5575 | MTL5042 |
MTL4541 | MTL5582B | MTL5044 |
MTL4541 | MTL7728+ | MTL5049 |
Frequently Asked Questions
Q: Does your goods are new and original?
A: Yes, they are new and original.
Q: How long warranty?
A: One-year warranty.