Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
Power dissipation | 0.75 W | |
Power consumption | 0.75 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Input | ||
Compensation (reference junction CJC) | internal cold junction compensation or external cold junction | |
temperature input | ||
Number of channels | 4 | |
Suitable field devices | ||
Field device [2] | Thermocouple | |
Field device [4] | mV source | |
Suitable sensors | ||
Sensor | thermocouples U, B, E, T, K, S, R, L, J, N, Pallaplat and mV sources | |
Connection | channel I: 1+, 2-; channel II: 5+, 6-; channel III: 9+, 10-; channel IV: 13+, 14- | |
Measuring range | -65 ... 75 mV with LFD , -75 ... 75 mV without LFD | |
Smallest span | 5 mV for 0.1 % accuracy | |
Linearity error | 0.1 % | |
Conversion time | max. 300 ms (4 channels) without LFD max. 600 ms (4-channel) with LFD | |
Compensation (reference junction CJC) | internal cold junction compensation or external cold junction | |
Line fault detection | can be switched on/off for each channel via configuration tool , | |
Open-circuit | > 1 kΩ | |
Transfer characteristics | ||
Deviation | ||
Influence of ambient temperature | max. 0,1 %/10 K | |
Indicators/settings | ||
LED indication | Power LED (P) green: supply Status LED (I) red: line fault (collective alarm) , red flashing: communication error | |
Coding | optional mechanical coding via front socket | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Environmental test | EN 60068-2-14 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Damaging gas | EN 60068-2-42 | |
Relative humidity | EN 60068-2-78 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Altitude | max. 2000 m | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 when mounted on backplane | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 150 g | |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 03 ATEX 2042 X | |
Marking | ![]() ![]() ![]() | |
Input | ||
Voltage | 1 V | |
Current | 71 mA | |
Power | 62 mW (trapezoid characteristic curve) | |
Certificate | PF 08 CERT 1234 X | |
Marking | ![]() | |
Galvanic isolation | ||
Input/input | functional insulation acc. to IEC 60664-1:2007, rated insulation voltage 50 V, testing voltage 500 V | |
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 | |
International approvals | ||
ATEX approval | PTB 03 ATEX 2042 X | |
UL approval | E106378 | |
Control drawing | 116-0322 | |
IECEx approval | ||
IECEx certificate | IECEx BVS 09.0037X | |
IECEx marking | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I | |
General information | ||
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Company Introduction:
Achievers Automtation Limited deals with a complete range of industrial automation components and instruments with more than 12 years’ experience, and always try best to provide quality goods and timely services to our valued customers from over 45 countries worldwide.
Achievers serves the Oil & Gas industries, EPC contractors, System Integrators and other industrial automation and process control companies worldwide. The industries we serve include Oil & Gas, Chemical, Petrochemical, Mining, Energy & Utilities, Pharmaceuticals, Electronics, Food and etc.
The company provides a diversified range of products to meet any process control and automation challenges in the industry. We stock and distribute pressure & temperature transmitters, level controller & transmitters, temperature probes, flowmeter, vibration monitoring devices, chart recorders, sensors, PLC, DCS, HMI, measuring instruments and other field instruments.
Below are the TOP BRANDS we handle in the past 12 years:
Bently Nevada 3500 Vibration Monitoring System&3300 Proximity Probes, Sensors & Transducer Systems
ALLEN BRADLEY Industrial Control Products
Pepperl-Fuchs Industrial Sensors & Isolated Barrier
MTL Instruments Isolated Barrier
Endress+Hauser Flow, Level, Liquid Analysis Instrument
YOKOGAWA DCS & Field Instruments & Process Analyzers
Rosemount Analytical Products
ASCO Solenoid Valves
FISHER Valve&Positioner
IFM Sensors & Controllers
ABB V18345 Valve Positioner
ABB Bailey Infi 90 and Net 90 Modules
FISHER DLC3100 Digital Level Controller
TELEDYNE Oxygen Sensor & Fuel Cell
HONEYWELL Switches & Transmitter
VEGA Level Measurement Products
AUMA Electric Actuators and Gearboxes
SMC Controls, process, and Industrial products
SICK Industrial Sensors
FESTO Pneumatic & Electric Automation Products
YASKAWA Industrial Ac Drives
BECKOFF Controllers & I/O Modules
BALLUFF Linear Position Sensors
SCHMERSAL Safety switches & Safety Systems
FAQ of Achievers
Q:Are the Products Genuine OEM Units?
A: These items have been certified by Achievers Automation Limited to be genuine OEM Units obtained through OEM or independent third-party channels.
Q:How will you arrange shipment?
A: We can arrange shipment based on your request. We have cooperated forwader who can arrange shipment via FedEx, DHL,TNT with good price.
Q:What is the warranty of goods?
A: One-year Warranty.