Specification
Product type : Temperature Converter
Number of channels : Two
Signal source : THC types J, K, T, E, R, S, B or N to BS 60584 and XK mV input
Location of signal source : Zone 0, IIC, T4–6 hazardous area Division 1, Group A, hazardous location
Input signal range : –75 to +75mV
Input signal span : 3 to 150mV
Response time : Configurable - 500 ms default (Accuracy at 100/200ms - contact Eaton's MTL product line)
LED indicator Green: power and status indication Yellow: one provided for channel status Red: alarm indication
Power requirement, Vs with 20mA signal : 60mA at 24V
Power requirement, Vs with 20mA signal : 60mA at 24V
Isolation : Functional isolation channel–channel for safe and hazardous–area circuits
Configurator : A personal computer running MTL PCS45 software with a PCL45USB serial interface.