MTL5522 MTL Instruments Solenoid/ Alarm Driver
MTL5522 is a loop-powered module which enables a device located in the hazardous area to be controlled from the safe area. TheMTL5522 can drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED. The unit'sinput/output isolation allows the control switch to be connected into either side of the 24V dc supply circuit
Product type : Solenoid/ Alarm Driver
Number of channels : One
Location of load : Zone 0, IIB, T4–6 hazardous area if suitably certified Div. 1, Group C hazardous location
Input voltage : 20 to 35V dc
Hazardous-area output : Minimum output voltage: 10.7V at 70mA, Maximum output voltage: 24V from 158?, Current limit: 70mA minimum
Output ripple : < 0.5% of maximum output, peak to peak
Response time : Output within 10% of final value within 100ms
LED indicator: Yellow: output status, on when output active
Maximum current consumption : 125mA (typ.) at 24V
Power dissipation within unit : 1.4W at 24V
Safety description : Uo=25V, Io=166mA, Po=1.04W, Um = 253V rms or dc