The MTLx511 enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous-area. When selected, open MTL4511 1-channel safety barriers PROXIMITY DETECTOR INTERFACE or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module.Phase reversal for the channel is selected by a switch on the side of the module and output is provided by changeover relay contacts
Product type : Switch/Proximity Detector Interface 1-channel, with line fault detection
Response time: 10ms maximum
Contact rating(Safe Area):10W, 0.5A,35V dc
Contact rating(Zone 2):10W, 0.5A,35V dc
Response time : 10ms maximum
Contact rating(Safe Area) :10W, 0.5A,35V dc
Contact rating(Zone 2) :10W, 0.5A,35V dcNumber of channels : One
Location of switches : Zone 0, IIC, T6 hazardous area,Div. 1, Group A hazardous location
Input/output characteristics : Normal phase, Outputs closed if input > 2.1mA (< 2kO in input circuit), Outputs open if input < 1.2mA (> 10kO in input circuit), Hysteresis: 200µA (650O) nominal