The MTL5049 isolates and passes on two 4/20mA signals from a controller located in the safe area to two loads located in the hazardous area.
Number of channels
Two
Location of loads
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Safe-area input
Signal range: 4 to 20mA
Under/over range: 0 to 24mA
Hazardous-area output
Load resistance: maximum 550Ω (11V at 20mA)
Output resistance
>2MΩ
Input and output circuit ripple
<40µA peak-to-peak
Transfer accuracy at 20°C
Better than 20µA
Input voltage drop
<4V at 20mA
Response time
Settles to within 10% of final value within 250µs
Temperature drift
<1µA/°C