Model | AIM-M10 | AIM-M100 | AIM-M200 | |
Power supply | Voltage | AC220V±10% | AC220V±10% | DC24V±25% |
Frequency | 50/60Hz | 50/60Hz | - | |
Max power consumption | <5W | <8W | <3W | |
Insulation monitoring | Insulation resistance measuring range | 10-999kΩ | ||
Relative percentage accuracy | 0—±10% | |||
Alarm value range | 10—995kΩ | 50—999kΩ | 50—999kΩ | |
Response time | <2s | |||
Measuring voltage | <12V | |||
Measuring current | <42uA | <50uA | <50uA |
Current monitoring | Measuring range | 2.1-50A | ||
Alamm value range | 5-50A | |||
Measurement accuracy | ≤±5% | |||
Temperature monitoring | Thermal resistor | PT100 | ||
Measuring range | -50—+200℃ | |||
Alarm value range | 0—+200℃ | |||
Alarm output | Output type | 1 channel relay output | 2 channels relay output(programmable) | 2 channels relay output |
Contact rating | AC 250V/3A DC 30V/3A | AC 250V/3A DC 30V/3A | AC 250V/3A DC 30V/3A | |
Environment | Working temperature | -10—+55℃ | ||
Storage temperature | -20—+70℃ | |||
Relative humidity | 5%-95%,non-condensing | |||
Altitude | ≤2500m | |||
Communication | RS485 interface,Modbus-RTU protocol | RS485 interface,Modbus-RTU protocol | CAN interface, custom protocol, RS485 interface, Modbus-RTU protocol |