AKH-0.66/Z integrated current transforemer
Product feature
Combined current transformer is also called the three-phase current transformer. As current signal acquisition device, it is generally matched with multi-loop current monitoring device (AMC16), PZ300, moulded case circuit breaker and other products. It can save installation space, reduce the cumbersome wiring, be convenient to use and effectively reduce the cost.
| ||||||||||||||||
Specification | ratio(A) | Precision degree and corresponding rated load (Ω) | Straight-through tums | Max. cable outer diameter (mm) | ||||||||||||
0.2 | 0.5 | 1.0 | ||||||||||||||
Z-2×Φ10 | 50A/25mA | 10 | 1 | Φ10 | ||||||||||||
Z-3×Φ20 | 5/5(1) | 1.5 | 20 | Φ20 | ||||||||||||
10/5(1) | 1.5 | 10 | ||||||||||||||
15/5(1) | 1.5 | 8 | ||||||||||||||
20/5(1) | 1.5 | 5 | ||||||||||||||
25-30/5(1) | 1.5 | 4 | ||||||||||||||
50-75/5(1) | 1.5 | 2 | ||||||||||||||
100/5(1) | 1.5 | 1 | ||||||||||||||
150/5(1) | 1.5 | 1 | ||||||||||||||
200/5(1) | 2.5 | 1 |
Z-3×Φ35 | (100-150)A/5(1)A | 2.5 | 1 | Φ35 | Fixed by base p late screw | |||
200A/5(1)A | 1.5 | 1 | ||||||
250A/5(1)A | 3.75 | 1 | ||||||
(300-450)A/5(1)A | 5 | 1 | ||||||
(500-800)A/5(1)A | 10 | 1 | ||||||
(1000-1250)A/5(1)A | 10 | 1 |
Dimension
Manufacturer Company