AMC16Z series multi channel din rail ac power meter is independently designed to meet the needs of the increasingly high precision power distribution management requirements of the data center. It is suitable for carious all-round inrelligent monitoring of terminal distribution equipment.
Technical parameter
Technical parameters | AMC16Z-FAK24 | AMC16Z-FAK48 | |
Measurement parameters | Voltage, current, frequency, active power, reactive power, power factor, active power, reactive power, switching state | ||
2-31 times harmonics | |||
Bus Voltage | Rated | 220VAC | |
Measurement | ±20% | ||
Overload | Instantaneous voltage 2 times/second | ||
Current | Rated | 50mA | |
outgoing line loop | Range | 0.125~60mA | |
Overload | Duration 1.2 times, instantaneous 10 times/second | ||
Input frequency | 45~60Hz | ||
Measurement accuracy | Outgoing line | Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1 | |
Auxiliary power supply | Power supply by AMC16Z-ZA | ||
Environment | Temperature | Working:-15℃~55℃ Storage:-25℃~70℃ | |
Humidity | Relative humidity | ||
Altitude | ≤2500m | ||
Communication | RS485/Modbus-RTU | ||
Installation method | DIN35mm Guide rail or bottom plate mounting | ||
IP grade | IP20 | ||
Class of pollution | 2 |