● Temperature and humidity measuring & controlling
● Panel mounted
Technical Parameter | | Value | |
Measuring range | Temperature | -40.0℃~99.9℃ | |
| Humidity | 20%RH~90%RH | |
Accuracy | Temperature | ±1℃ | |
| Humidity | ±5%RH | |
Analog output | | DC 4~20mA | |
Set range of controlling parameter | Heating for Temperature rising | -40.0℃~40.0℃ | |
| Blowing for temperature decreasing | 0℃~99.9℃ | |
| Humidity control | 20%RH~90%RH | |
Contact capacity | | 5A/AC250V | |
Communication | | RS485(MODBUS-RTU) | |
Auxiliary power supply | Working range | AC 85~265V DC 100~350V | |
| Consumption | Basic power consumption(≤0.8w)+ relay power consumption(each channel≤0.7w) | |
Insulation resistance | | ≥100MΩ | |
Environment | Temperature | -20℃~+60℃ | |
| Humidity | ≤95%RH(No condensation) | |
| Altitude | ≤2500 m |