The AIM-M200 monitors the insulation resistance of medical IT system, At the same time, the load current and temperature of the IT system transformer is monitored. In combination with ASG100, AIL100 series insulation fault locators and the appropriate measuring current transformers, the AIM-M200 is designed to support insulation fault location
Main Characteristics
● Insulation monitoring for medical IT systems
● Load and temperature monitoring of isolation transformer
● Device disconnection monitoring
● LED indicators: On, Insulation, Overload, Overtemp
● Alarm relay output
● Test button
● Insulation fault location
● RS485 (MODBUS-RTU) + CAN (custom protocol
Technical Parameters
Input voltage | DC 18~36V |
Power consumption | ≤3VA |
Resistance measuring range | 10~999kΩ |
Response value | 50~999kΩ |
Relative uncertainty | ±10% |
Response time | ≤3s |
Measuring voltage U | ≤12V |
Measuring current I | ≤50uA |
Load current monitoring Measuring Value | 2.1~50A |
Load current monitoring Alarm Value | 5~50A |
Load current monitoring Measuring accuracy | ±5% |
Dimension(mm)