AEW 100 is a multifunction power meter. There are functions like RS485 communication and Lora communication on 470MHz. With build-in MODBUS-RTU protocol, AEW100 can match most of the system integrate requirement. AEW100 has the advantage of higher accuracy, more compact and easy installing.
Technical Features
ADW2xx series subject Technical parameter
Auxiliary power | AC/DC 85~265V;consumption≤10VA; | |
Input | Frequency | 45~65Hz; |
Voltage | AC 3×220V/380V; Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s; Power consumption:≤ 0.5VA; | |
Current | AC 5A,100A,400A,600A;(External opening transformer); Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s; Power consumption:≤ 0.5VA; | |
measurement accuracy | Frequency 0.05Hz, voltage and current 0.5 level, active electric energy level 1, reactive electric energy level 2; 2-31 times harmonic accuracy: ± 1%; | |
Features | Pulse output | Output mode: optocoupler pulse with open collector; |
Communication | RS485,Modbus-RTU;Baud rate 1200~38400; | |
Switching Input | Dry contact input,Built in power supply; | |
Switching Output | Output mode:Relay normally open contact output; contact rating:AC 250V/3A DC 30V/3A; |
ADW2xx series Module technical parameters
Switching Module | Power | RJ45 interface,DC 12V,Power consumption≤1W; |
Communication | RJ45 interface,Modbus-RTU;(Communication with the main Part) ; | |
Switching input | Dry contact input,Built in power supply; | |
Switching output | Output mode:Relay normally open contact output; contact rating:AC 250V/3A DC 30V/3A; | |
Temperature and leakage module | Power | RJ45 interface,DC 12V,Power consumption≤1W; |
Communication | RJ45 interface,Modbus-RTU;(Communication with the main Part) ; | |
Temperature measurement | -20~100℃ | |
Leakage measurement | 10~3000mA; | |
Measurement accuracy | temperature ±2℃,Leakage1.0%; |