Cleanroom Equipment SUS304 Negative Pressure Laminar Flow Powder Weighing Booth
CUSTOMIZED DESIGN IS AVAILABLE
Installation
We offer a full range of cleanroom installation capabilities. This can include full turnkey projects that include all plant, ductwork, walls,
floors, ceilings, control systems, internal fittings, storage equipment, site management, final validation and staff training.
Alternatively we can operate as your nominated subcontractor concentrating solely on one or more components of the overall project.
Quicky Detail:
Purification rank: Class100
Three Step Filtration System
Fluid seal Mini-pleats HEPA filter
99.995%@0.3um H13
GMP Standard with DOP port testing
Air speed:0.3-0.6m/s
Power: 380V/60HZ or 415V/50HZ
Applications: dispensing booth subdivision of powder of liquids, charging and offloading materials to reactors, fluid bed dryers, granulators,
filter dryers, glass ware skids in clean rooms and so on.
Operating Features:
1: dispensing booth modular. Easy-to clean rigid design with minimal joints
2: HEPA/ULPA Gel-seal down flow filter are replaceable from within the booth. Gel-seal is more reliable than conventional gasket seals
3: Voltage-compensating blowers ensure stable air flow.
4: Magnehelic Gauges provide convenient and reliable means for monitoring gauges air flow and filter condition.
5: Containment performance verified according to the ISPE good practice guide, assessing the particulate containment performance of pharmaceutical equipment.
Products Parameter:
MODEL | KEL-DB1000 | KEL-DB1500 | KEL-DB2000 |
External size (mm) (W*D*H) | 1200x1500x2400mm | 1500x1700x2400mm | 2000x1800x2400mm |
Work zone (mm) (W*D*H) | 1100x1200x2000mm | 1400x1200x2000mm | 1900x1300x2000mm |
Purification rank | Class 100(ISO5) | ||
Air speed | 0.45m/s +_20% | ||
Material (Option) | 1: Entirety Stainless Steel 201/304/316.(T=1.2/1.5mm) 2: External and internal side is steel with power coated. (T=1.2/1.5mm) | ||
Control system | 1: Air Speed according to frequency converter control . 2: Gel Sealant High Efficiency HEPA air filter for high purification rank 3: Wind speed detection, Constant temperature and constant humidity Detector according to client request install 4: DOP/PAO Port and differential Pressure Guage for HEPA /secondary filter so that remind of you change the air filter in time 5: 5 different filter configuration available utilizing combination of G4,F8.H13,H14 and PLF Screens . 6; GMP Modular design with minimized joints and seams. 7: PVC strip curtains available 8; Energy Efficient high air volume fan to minimize operating cost, | ||
Noise level(dB) | <65dB | ||
Filter step | 3 Step | ||
HEPA filter | 99.995% @ 0.3um Gel sealant mini--pleats HEPA Air Filter | ||
Secondary filter | F8 pocket air filter | ||
Pre-filter Efficiency | G4 Z-Line panel air filter | ||
Power supply | 380V/50HZ OR 220V/50HZ | ||
Packing material | Standard Export Poly wood Packing(Fumigant free material) |