Cleanroom Terminal HEPA Filter Housing Cassette H13/ H13 HEPA Filter Boxes
Detial
The HEPA Replacement Air Filter ensures it yields only clean filtered air from the filter face, when connected to a duct system or fan via its spigot connection on the rear of the filter.
the cassette casing is the integral case of the HEPA filter as well.
(No clamping pressures, gasket seals and the quality of the sealing mating face, associated with the traditional Terminal Housing.)
Once connect to the round inlet duct , only filtered air can leave the filter, as individual testing before leaving factory
casing:extruded Aluminum frame
ceiling connect plate: galvanized or cooled-roll steel
Sealant:polyurethane
separator:Hot-melt
Gasket:EVA 5mm
Filter media:mini pleat Glass fiber
thermal insulation PEF fiber : on request
distribution plate: on request
Duct: 8cm height,
Diameter : 250 mm (10 inches )or 300 mm(12 inches )
(others duct diameter or request ; inlet collar designed
with continuous rib to help retain the ductwork on collar.)
Use the highest temperature, humidity:80℃,80%
Parameter
Dimensions(mm) | Rated a ir flow @0.45m/s |
Initial Resistance Under Standard air flow | |||||
HEPA | ULPA | ||||||
A | B | C | M3/h | In.W.G. | Pa | In.W.G. | Pa |
600 | 600 | 150 | 600 | 0.50 | 125 | 0.58 | 145 |
600 | 915 | 150 | 900 | 0.50 | 125 | 0.58 | 145 |
600 | 1210 | 150 | 1200 | 0.50 | 125 | 0.58 | 145 |
600 | 600 | 220 | 600 | 0.32 | 80 | 0.36 | 90 |
600 | 915 | 220 | 900 | 0.32 | 80 | 0.36 | 90 |
600 | 1210 | 220 | 1200 | 0.32 | 80 | 0.36 | 90 |
Operation temperature | 80 celsius degree(158F),aluminum foil,fiberglass,and insulated cotton enclosed on the back. | ||||||
Cabinet | Sand acid and pressed aluminum,standard frame | ||||||
Sealed material | The seal spacer is installed on the air outlet unless clients require not. | ||||||
The positioning of protective net | Air leaving side | ||||||
Filtering paper | High efficiency particulate air filters(fiberglass paper,0.3 micron,efficiency of 99.99%) | ||||||
Options | Ulpa Air Filter(waterproof fiberglass,0.3micron,efficiency of 99.9995%) | ||||||
Smooth outline | |||||||
No protective net | |||||||
Separator and airflow controller | |||||||
Adjustable diffuser plate with separator | |||||||
300mm(12'')adapter tube of air supply |
Advantages:
1. Aluminium frame and cover are antirust.
2. By standard diffuse mesh ,the airflow will be fluent.
3. Inlet tube could prevent loss of air.
4. Use special resin of without phosphorus to seal the media and frame absolutely.
5. Do not allow for break up and blocking of wind velocity.