Specifications
Brand Name :
Sanwu
Model Number :
YJLV
Certification :
ISO CCC
Place of Origin :
Henan
MOQ :
1000M
Price :
Negotiable
Payment Terms :
L/C, T/T, Western Union
Supply Ability :
200 tons per day
Delivery Time :
1-15days
Packaging Details :
Export steel or wooden drum
Material :
Cu/Al+xlpe/pe/pvc
Voltage :
Under 35kv
Standard :
IEC,ASTM,BS,DIN,NFC,CSA
Description

Low Voltage XLPE PVC Insulated Armoured Flexible Electric (YJV/YJV22-0.6/1KV) Power Cable

Application:

This product is suitable for power transmission and distribution line of rated voltage (U0/U) 0.6/1.0KV line.

Technical Parameter:

When the cable is running normally, the Maximum temperature of conductor is 90℃; and is 250 ℃ when the short circuit (Max. last 5s) happens.

The ambient temperature of installation shall not lower than 0 degrees.

Minimum bending radius is 12 D (“D” refers to cable diameter)

  • Complete Cable:
    • One phase conductor, and one neutral conductor are insulated with Extruded Cross-Linked Polyethylene (XLPE) and jacketed with Extruded High-Density Cross-Linked Polyethylene (HDXLPE)
    • Twisted cables form duplex assembly
    • Manufactured and tested in accordance with ANSI/ICEA Standard S-81-570
    • When specified, cable is produced in accordance with UL 854 and listed as a Type USE-2 cable
  • Conductors:
    • Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231 or B786
  • Insulation & Jacket:
    • Insulation is Extruded Black Cross-Linked Polyethylene (XLPE)
    • Jacket is Extruded High-Density Cross-Linked Polyethylene and meets requirements of ASTM D1248, Type III
    • The phase conductor is black, and the neutral conductor is black identified by three extruded yellow stripes.

Jacketed Aluminum Duplex Conductor Underground Power Cable Features and Benefits:

  • Insulation/Jacket system provide high degree of protection against insulation damage
  • For NEC-complying applications, the maximum conductor operating temp is 90°C in wet or dry locations
  • Also suitable for non-code-complying installations with a temperature of 90°C in wet or dry locations in accordance with ICEA specifications

Jacketed Aluminum Duplex Conductor Underground Power Cable Applications:

  • Intended for use in underground systems operated at 600 volts or less.

Jacketed Aluminum Duplex Conductor Underground Power Cable Options:

  • Aluminum 1350-H16 conductor
  • Copper conductors
  • Other neutral identification methods
  • CDC Combined Duct & Cable
  • Reeless Package
  • PE Insulated/HDPE Jacketed rated 75°C, Type UD-S
  • Type USE-2 per UL 44

Single Core Cable

Nominal cross section Nominal Thickness of Insulation Nominal thickness of Sheath Approx. Overall Diameter of Cable Approximate weight of cable Conductor DC resistance Test voltage Cable Current
In the air Buried in soil
Cu AL Cu AL Cu AL Cu AL
mm² mm mm mm Kg/km Kg/km Ω/km Ω/km kv/5min A A A A
1*1.5 0.7 1.5 6 53 53 ≤12.1 ≤12.1 3.5 26 26 33 32
1*2.5 0.7 1.5 6 68 ≤7.41 3.5 34 43
1*4 0.7 1.5 7 87 64 ≤4.61 ≤7.41 3.5 44 35 56 42
1*6 0.7 1.5 7 110 73 ≤3.08 ≤4.61 3.5 56 45 70 54

Two Cores Cable

Nominal cross section Nominal Thickness of Insulation Nominal thickness of Sheath Approx. Overall Diameter of Cable Approximate weight of cable Conductor DC resistance Test voltage Cable Current
In the air Buried in soil
Cu AL Cu AL Cu AL Cu AL
mm² mm mm mm Kg/km Kg/km Ω/km Ω/km kv/5min A A A A
2*2.5 0.7 1.8 11.8 151 118 ≤7.41 ≤12.1 3.5 26 20 35 27
2*4 0.7 1.8 12.7 198 146 ≤4.61 ≤7.41 3.5 34 27 45 36
2*6 0.7 1.8 13.7 250 173 ≤3.08 ≤4.61 3.5 43 35 57 46
2*10 0.7 1.8 16.3 374 245 ≤1.83 ≤3.08 3.5 60 47 77 59

Three Cores Cable

Nominal cross section Nominal Thickness of Insulation Nominal thickness of Sheath Approx. Overall Diameter of Cable Approximate weight of cable Conductor DC resistance Test voltage Cable Current
In the air Buried in soil
Cu AL Cu AL Cu AL Cu AL
mm² mm mm mm Kg/km Kg/km Ω/km Ω/km kv/5min A A A A
3×1.5 0.7 1.5 10 145 - ≤12.1 - 3.5 20 - 27 -
3×1.6 0.7 1.5 11 185 140 ≤7.41 ≤12.1 3.5 26 20 35 27
3×4 0.7 1.5 12 250 175 ≤4.61 ≤7.41 3.5 34 27 45 36
3×6 0.7 1.5 13 320 210 ≤3.08 ≤4.61 3.5 43 35 57 46
3×10 0.7 1.5 15 450 260 ≤1.83 ≤3.08 3.5 60 47 77 59

Four Cores Cable

Nominal cross section Nominal Thickness of Insulation Nominal thickness of Sheath Approx. Overall Diameter of Cable Approximate weight of cable Conductor DC resistance Test voltage Cable Current
In the air Buried in soil
Cu AL Cu AL Cu AL Cu AL
mm² mm mm mm Kg/km Kg/km Ω/km Ω/km kv/5min A A A A
4×4 0.7 1.5 13 253 155 ≤4.61 ≤7.41 3.5 34 27 45 36
4×6 0.7 1.5 14 337 184 ≤3.08 ≤4.61 3.5 43 35 57 46
4×10 0.7 1.5 16 501 258 ≤1.83 ≤3.08 3.5 60 47 77 59

YJV22 LV Power Cable

Send your message to this supplier
Send Now

YJV22 LV Power Cable

Ask Latest Price
Brand Name :
Sanwu
Model Number :
YJLV
Certification :
ISO CCC
Place of Origin :
Henan
MOQ :
1000M
Price :
Negotiable
Contact Supplier
YJV22 LV Power Cable

Luoyang Sanwu Cable Co., Ltd.,

Verified Supplier
5 Years
henan, luoyang
Since 2016
Business Type :
Manufacturer, Exporter
Total Annual :
10000000-30000000
Employee Number :
50~200
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement