BS DIN Standard AAC Ant Conductor Overhead AAC Bull Conductor
AAC Ant Conductor AAC Bull Conductor is widely used in overhead power transmission lines with various voltage levels because they are such good characteristics as simple structure, convenient installation, and maintenance,low cost large transmission capacity.
Service Performance
(1).The permissible long-time operating temperature for aerial conductor is 70oC.
(2).Under the circumstance that rare climate occurs and high ice coverage rate, the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
(3).Under installation, the arc downing stress of all the conductors should be the same. With in the permissible distance of crossing buildings or dropping to the ground, the stress can be 10-15% higher than regular stress.
We can supply this conductor according to different recognized standards, such as IEC61089, BS215, BS EN 50182: 2001, STM B231, CSA C49, DIN480201, JIS C3109, customer special specification also can be satisfied.
area | Stranding &wire diameter | Approx Overall diameter | Breaking Load | DC Resistance at 20 | Weight |
mm | mm | N | Ω/km | Kg/km | |
16 | 7/1.70 | 5.10 | 2840 | 1.802 | 43.5 |
25 | 7/2.15 | 6.45 | 4355 | 1.127 | 69.6 |
35 | 7/2.50 | 7.50 | 5760 | 0.8332 | 94.1 |
50 | 7/3.00 | 9.00 | 7930 | 0.5786 | 135..5 |
70 | 7/3.60 | 10.80 | 10950 | 0.4018 | 195.1 |
95 | 7/4.16 | 12.48 | 14450 | 0.3009 | 260.5 |
120 | 19/2.85 | 14.25 | 19420 | 0.2373 | 333.5 |
150 | 19/3.15 | 15.75 | 23310 | 0.1943 | 407.4 |
185 | 19/3.50 | 17.5 | 28440 | 0.1574 | 503.0 |
210 | 19/3.75 | 18.75 | 32260 | 0.1371 | 577.4 |
240 | 19/4.00 | 20.00 | 36260 | 0.1205 | 656.9 |
300 | 37/3.20 | 22.40 | 46850 | 0.09689 | 820.4 |
400 | 37/3.70 | 25.90 | 61150 | 0.07247 | 1097 |
500 | 37/4.16 | 29.12 | 76370 | 0.05733 | 1387 |
630 | 61/3.63 | 32.67 | 91940 | 0.04577 | 1744 |
800 | 61/4.10 | 36.90 | 115900 | 0.03588 | 2225 |