EVADA HQ-G High frequency online ups uninterrupted power supply three in three out 10KVA 15KVA 20KVA
Parameters:
Model | HP1000G | HP1500G | HP2000G | HP3000G-240V | |
Capacity | 10000VA | 15000VA | 20000VA | 30000VA | |
Input | |||||
Rated voltage | 380 VAC(3P+N) | ||||
voltage range | 190~520 VAC (3 phase) @50% load; 305~478 VAC (3 phase) @100% load | ||||
Frequency Range | 46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system | ||||
Power factor | ≧ 0.99 @100% load | ||||
Output | |||||
Output Voltage | 360/380/400/415VAC (3P+N) | ||||
Voltage accuracy | ± 1% | ||||
Frequency range (synchronization range) | 46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system
| ||||
Frequency range (battery mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||
Overload capability | City power mode | 100%~110%: 10 minutes; 110%~130%: 1 minute>130%: 1 second | |||
Battery mode
| 100%~110%: 30 seconds; 110%~130%: 10 seconds; >130%: 1 second
| ||||
Power factor | Standard 0.8 (optional 0.9) | ||||
Current peak ratio | 3:1 | ||||
Harmonic distortion | ≦ 2 % @ 100% linear load ≦ 5 % @ 100% non-linear load | ||||
Switching time
| City power-battery
| 0ms | |||
Invert-bypass | 0ms | ||||
effectiveness | |||||
Inverter mode | >90.5% | >91.5% | >91.3% | ||
Battery | |||||
Battery Qty | The default 20 sections (16~20 adjustable) | ||||
recharging current | 8 A ± 10% | 12 A ± 10% | |||
Charging voltage | 273VDC±1% | ||||
Physical characteristics | |||||
Dimensions Deep X Width X Height (mm) | 592X250X576 | 815X250X826 | |||
N.W (kg) | 38 | 40 | 64 | ||
Environmental conditions | |||||
Operating environment | Relative humidity 0-95% and temperature 0-40 ° C (no condensation) | ||||
noise | Less than 60 dB(A) @ 1 meter | Less than 65 dB(A) @ 1 meter | |||
management | |||||
Smart RS-232 or USB | Support Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix,and MAC | ||||
Optional SNMP | Support for power management by SNMP administrators and web browsers |
Company Information: