Evada High Frequency Online Rack mount UPS extension machine power supplies pure sine wave10kva 15kva 20kva
Parameters:
Model | HQ3110GR(L) | HQ3115GR(L) | HQ3120GR(L) | |
Capacity | 10000VA | 15000VA | 20000VA | |
Input | ||||
Rated voltage | 380 VAC(3 Phase+N) | |||
Voltage Range | 190~520 VAC@50% load;305~478 VA@100% load | |||
Frequency Range | 46Hz ~ 54 Hz @ 50Hz system;56Hz ~ 64 Hz @ 60Hz system | |||
Power Factor | ≧ 0.99@100% load | |||
Output | ||||
The output voltage | 208/220/230/240VAC | |||
Voltage accuracy | ± 1% | |||
Frequency range (synchronization range) | 46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system | |||
Frequency range (battery mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | |||
Overload capability | Mains mode | 100%~110%: 10 minutes;110%~130%: 1 minute;>130% : 1 second | ||
Battery mode | 100%~110%: 30 seconds;110%~130%: 10 seconds;>130% : 1 second | |||
Power factor | Standard 0.8 (Optional 0.9) | |||
Current peak ratio | 3:1 | |||
Harmonic distortion | ≦ 2 % @ 100% Linear load; ≦ 5 % @ 100% Nonlinear load | |||
Switch time | Mains - battery | 0ms | ||
Inverter - Bypass | 0ms | |||
Effectiveness | ||||
Inverter mode | > 90% | |||
Battery | ||||
Standard machine | battery model | 12 V / 7 Ah | ||
Number of batteries | Preset 16 (16-20 adjustable) | Preset 2 x 16 (16-20 adjustable) | ||
recharging current | 1A ± 10% | 2A ± 10% | ||
Charging voltage | 218.4VDC ± 1% | |||
Long extension machine | Number of batteries | Default 16 (16-20 adjustable) | ||
recharging current | 4 A ± 10% | |||
Charging voltage | 218.4VDC ± 1% | |||
Physical characteristics | ||||
Standard machine | Dimensions Deep x Width x Height (mm) | UPS Host: 668 x 482.6 x 133[3U] Baterry Box: 580 x 482.6 x 133[3U] | UPS Host: 668 x 482.6 x 266[6U] Baterry Box : 580 x 482.6 x 133[3U] x 2 pcs | |
net weight (kg) | UPS Host: 22 Baterry Box: 63 | UPS Host: 45 Baterry Box: 63 x 2 pcs | ||
Long extension machine | Dimensions Deep x Width x Height (mm) | 668 x 482.6 x 133[3U] | 668 x 482.6 x 266[6U] | |
Net Weight (kg) | 22 | 45 | ||
Environmental conditions | ||||
Operating environment | Relative humidity 0-95% and temperature 0-40 ° C (no condensation) | |||
Noise | Less than 60 dB(A) @ 1 meter | Less than 60 dB(A) @ 1 meter | ||
Control management | ||||
Smart RS-232 or USB | Support for Windows®2000/2003/XP/Vista/2008/7/8,Linux and MAC | |||
Optional SNMP | Support for power management by SNMP administrators and web browsers |
Application field
Local area network server, communication base station server, SME data room, financial system small network, industrial automation control system, etc.
Company Information: