Features:
●360° monitoring range.
●automatic fire detecting.
●Automatic fire tracking.
●Automatic fire targeting.
●Automatic fire extinguishing.
●No fault alarming,no miss alarming.
●Continuously fire extinguishing.
What's an Automatic Fire Water Monitor?
Our Automatic Fire Water Monitor are water hydraulic driven and discharge large volumes of suppression agent from a single fixed location, and at high pressure to give it an excellent range of coverage.The Quick Response Automatic Fire Water Monitor has built-in infrared thermal imaging detector, UV flame detector, closed circuit television camera. Real time dynamic flame location and laser corrector. The Automatic Fire Water Monitor works with the external UV flame detector to eliminate the detection blind area and increase early warning range.
When the Automatic Fire Water Monitor receives the fire early warning signal (UV or IR signal),it's built-in image IR flame detector will automatically rotate along with the water monitor and lock the flame very quickly, then open pump and valve to spray water to extinguish the fire. Otherwise, the water monitor will consider it as a false alarm, and the Automatic Fire Water Monitor will reset automatically.The time spent from fire started to fire targeted is less than 30 seconds.It can continuously targeting fires in cover range and extingusihing them one by one.
Specifications:
ZDMS0.6/5S-LZII | ZDMS0.6/10S-LZII | ZDMS0.8/20S-LZII | ZDMS0.9/30S-LZII | ZDMS0.8/40S-LZII | ZDMS0.8/50S-LZII | |
Working Voltage | DC36V | DC36V | DC24V | DC24V | DC24V | DC24V |
Rated Pressure | 0.6MPa | 0.6MPa | 0.8MPa | 0.9MPa | 0.8MPa | 0.8MPa |
Protection Radius | ≤20m | ≤28m | ≤42m | ≤50m | ≤52m | ≤55m |
Rate of flow | 5L/s | 10L/s | 20L/s | 30L/s | 40L/s | 50L/s |
Installation Height | 6~15m | 6~15m | 8~35m | 8~35m | 8~35m | 8~35m |
Jet radius | ≤34m | ≤39m | ≤56m | ≤62m | ≤67m | ≤73m |
Positioning time | ≤30s | ≤30s | ≤60s | ≤60s | ≤60s | ≤60s |
Monitoring radius | 40m | 40m | 60m | 60m | 80m | 80m |
Flange Connection | DN50 | DN50 | DN80 | DN80 | DN100 | DN100 |
Notices:
1.The side of cannon with label”this side to wall” must be faced to wall when installed.
2.A gasket must be given between the flanges when install cannon to pipe.
3.Signal lines must connect to signal lines of cannon where it is 2m from cannon.
4.Operation panel installed near the exit and 1.5m from ground,and from where operator can see all cannnons controlled by this operation panel.
5.Pls take care when handling cannon as there is UV detector at the bottom of cannon.The UV detetor is fragile.
6.Make sure there is no barrier around the cannon to stop the cannon 360 degree rotate.
7.The ground lead of DVR,earth wire and Lightning protection wire of control console need be connected to your ground lead.
Applications:
Our Automatic Fire Water Monitor are wildly used in Industrial,commercial and residential fields.Such as airport, high-speed railway station, bus station, hotel atrium, museum, library, TV studio, gymnasium, science and technology museum, exhibition hall, convention center, theater, cinema, civic activity center, industrial plant, chemical plant, gas station, oil port,helicopter hangar, power plants, logistics centers, hospitals, large shopping malls, commercial complexes, colleges and universities, coal mines, warehouses and other places with large space.