HT11 6KL 6kva UPS Uniterruptible Power Supply Rack Mount Online Double Conversion
JET-HT11 6KL (R) Online High-Frequency UPS
6KVA
1/1 Phase
Power Factor 0.8
6-10KVA Online High-Frequency UPS, has tower and rack installation. It is an ideal power supply solution for small capacity scenes based on online dual transform technology, which can eliminate all kinds of power grid problems.
Such as Model HT11 6KL, is 6KVA rack type UPS, 1 phase in and 1 phase out, with power factor 0.8. Pure sine wave output does not destroy devices. Zero-minute transfer time is more reliable.
JET-HT11 series is applied in servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.
Key Features
1, High-frequency online double conversion design.
2, Advanced DSP numerical control technology application, the performance of UPS is more stable, more superior quality.
3, Pure sinewave output is more stable and reliable, do not destroy devices.
4, Microprocessor control ensures high reliability
5, Output power factor is 0.8
6, Wide input voltage range and frequency range fit to harsh power grid condition.
7, Rack mount Installation.
Specifications
Model technical parameters | 6K | 6KL (R) | |
Nominal Capacity | 6KVA/4.8KW | ||
Nominal | Voltage | 220VAC | |
AC Input | Nominal Frequency | 50Hz | |
Voltage Range | 120~275VAC ±5 | ||
Frequency Range | 45~55Hz ±0.5Hz | ||
Bypass Voltage | 80VAC × (1±5%) ~ 285VAC × (1±5%) | ||
Battery Input | Battery Pack | 192VDC (Optional up to 240V) | |
Batteries Capacity &Qty | 12VDC x 16 (Optional up to 20 sets) | ||
Charging Current | 4A | ||
AC Output | Voltage | 220VAC ±1% (Invert Output) | |
Frequency | 46~54Hz (Normal AC Input) 50Hz ±1% (Abnormal AC Input) | ||
Wave Form | THD<3% (Linear Load) Sine Wave, THD<8% (Non-Linear Load) | ||
Power Factor | 0.8 | ||
Overload Cap. | 105~125% Bypass after 1mins | ||
Communication & Monitoring Function | RS232, dry contact | ||
Tower Type | Weight (kgs) | 57 | 18 |
Dimension (W x H x D) (mm) | 248×620×500 | 248×460×500 | |
Rack Type | Weight (kgs) | 18 | 18 |
Dimension (W x H x D) (mm) | 640×130×440 | 640×130×440 |
Remark: 6KVA UPS also has tower installation type of machine, the differences are list as above.
Models:
H: High-frequency
T: Tower type
R: Rack type
L: Long run machine