Product Discription
WNS Condensing Steam Boiler
The production model is WNS. This is a horizontal internal combustion of three -way fuel (gas) a fast -charged integrated boiler with a wet rear design. The wool tank and ignition chamber are the first, the second is a gas pipe and the third is composed of an economist and capacitor.
This product is used for burning light oil, natural gas and so on. The fuel is fired from the burner, ignited by an electronic ignition rod, and burned under mildly positive furnace pressure. High smoke temperature after combustion enters the coil pipe through reflux chambers in 180 degrees, and enters the front smoke pipe.
Product Features
1. Reasonable design:
Horizontal internal combustion murder in three cycles, wet tail structure, 100% fire water design, 100% wave bladder, has good expansion, sufficient heat interval and reasonable structure.
2. High efficiency and energy saving:
The structure of the blast furnace, threaded pipes and large combustion chamber is reasonable, energy consumption is low and the efficiency of heat transfer is high.The thermal efficiency of boilers can exceed 96%, and if capacitors are installed, the efficiency can be super is 100%.
3. Manufacturing specifications:
Boiler components are manufactured according to national and international standards (ISO). Advanced production technologies are closely monitored at every stage of production to ensure product quality.
4. Large steam room:
Since steam drying helps to eliminate superfluous condensation, reduce fuel consumption, scale and prolong service life, coke has enough space to manage the fluctuations of load and peak value, and to provide steam for high qu drying Italy.
5. Duration and duration:
Excellent professional design, advanced production technology and rigorous quality control guarantee the quality of all boilers in the regions of Henan and Hebei.
6. Easy to maintain:
There is a portable front and back smoke door, and a back control hole for the control and cleaning of the oven. There are maintenance holes, mechanical holes and manual holes in the body, and the latter is fully considered in the drawing.
Technical Parameters
Main Technical parameters of WNS Condensing Steam Boiler | |||||||||
Item | Unit | WNS1 | WNS2 | WNS4 | WNS6 | WNS8 | WNS10 | WNS15 | |
Steam Capacity | t/h | 1 | 2 | 4 | 6 | 8 | 10 | 15 | |
Working Pressure | MPa | 1.0 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | |
Steam Temperature | ℃ | 184 | 193 | 193 | 193 | 193 | 193 | 193 | |
Feed Water Temperature | ℃ | 20 | 20 | 20 | 20 | 20 | 20 | 20 | |
Thermal Efficiency | / | ≥100% | |||||||
Fuel | / | Natural gas, liquefied gas, city gas, light oil | |||||||
Fuel Consumption | Natural gas | NM3/h | 67 | 135 | 273 | 408 | 547 | 681 | 1019 |
Liquefied gas | Kg/h | 54 | 109 | 217 | 328 | 438 | 547 | 823 | |
City gas | NM3/h | 145 | 293 | 585 | 880 | 1162 | 1466 | 2202 | |
Light oil | Kg/h | 58 | 116 | 230 | 341 | 470 | 573 | 872 | |
Gas Feed pressure | Natural Gas | mbar | 100-150 | 100-150 | 150-200 | 150-200 | 150-200 | 150-200 | 150-300 |
City Gas | mbar | 100-200 | 100-200 | 150-200 | 150-200 | 150-200 | 150-200 | 150-300 | |
Running water volume | M3 | 3.2 | 3.5 | 6 | 9 | 10.94 | 12.17 | 21.76 |
Note: the fuel consumption in the table is based on light oil low calorific value 42915KJ/Kg (10260Kcal/Kg), natural gas low calorific value 35588KJ/NM3 (8500Kcal/NM3) and liquefied gas low calorific value 45998KJ/Kg (11000Kcal/Kg). Calculation of low calorific value (16750KJ/NM3 (4000Kcal/NM3) of urban gas.
Shape and Interface Dimensions of WNS Condensing Steam Boiler | |||||||
Item | Unit | WNS6 | WNS8 | WNS10 | WNS15 | ||
Transport Dimension (L*W*H) | / | mm | 5132*2807*3958 | 6052*3146*4083 | 6096*3205*4525 | 7804*3465*3540 | |
Mainframe transport weight | / | t | 16 | 21 | 25 | 46 | |
Main Steam Valve Pipe Diameter | DN | mm | 125 | 125 | 150 | 200 | |
Feed Water Valve | DN | mm | 50 | 50 | 50 | 65 | |
Safety Valve Diameter | DN | mm | 2*80 | 2*80 | 2*80 | 2*100 | |
Drain Valve Pipe Diameter | DN | mm | 2*40 | 2*40 | 2*40 | 2*50 | |
Chimney Diameter | φ | mm | 600 | 600 | 750 | 1000 |
Remarks: We will reserve rights to change the above mentioned data due to continuous policy transformation and product improvement.