Cylinder For Environment-Friendly CO2 Fire Suppression System Without Pollution In Telecommunication Room
Fire suppression systems are designed to suppress or extinguish a fire in sensitive environments where water from a fire sprinkler is not a desired extinguishing agent. Common areas where you will find fire suppression systems include server rooms, engine rooms, flammable storage areas, museums, and data centers.
There are a few different types of agents that are used in a suppression system to suppress the fire. In server rooms and environments where you have personnel working in the area, you will usually find clean agent or inert gas suppression systems. In environments where there are few personnel or none at all, you will typically find CO2 fire suppression systems. The areas that you’ll find CO2 fire suppression systems include engine rooms, generator rooms, power stations, flammable liquid storage rooms, and around large industrial machines.
While CO2 fire suppression systems are highly effective at suppressing fires, the CO2 agent also poses a health risk when compared to the other agents. For this reason, you’ll find CO2 fire suppression systems most often in non-occupied environments.
Parameters
No. | Specification | Technical Parameter |
1 | Device Model | QME70 |
2 | Capacity | 70Ltr |
3 | Filling Volume of Gas | 42kg |
4 | Working Pressure | 5.7MPa |
5 | Max Working Pressure | 12.4MPa |
6 | Spraying Time | ≤60s |
7 | Max Filling Rate | 0.6kg/L |
8 | Power | DC24V/1.6A |
9 | Working Pressure of Releasing Device | Container Valve: 19±0.95MPa; Manifold: 15±0.75MPa |
10 | Nitrogen Pressure of Driving | 6.0±1.0Mpa(20℃) |
11 | Condition of Reserving Room for Container | Temperature: 0~50℃ |
Application
-It is suitable for putting out all kinds of the fires of flammable liquid and solid matter; gas fire in which power can be cut off before extinguishing the fire.
-paint-spraying room
-electronic computer room
-telecommunication room
-archives room
-boiler room
-control center
-hangar
-garage
-Library
Package
We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.