Cylinder for Inert Gas Argonite Fire Extinguishing System
Naturally occurring Gases often used as blends, these blends are used to reduce oxygen to below 15% and above 12%. Oxygen levels below 15% will not allow a fire to burn as the oxygen is simply not there to fuel the fire. Levels of Oxygen between 12% and 15% is adequate to sustain human life. Oxygen levels between 12% and 10% will show visible signs of effects asphyxiation Oxygen levels below 10% are extremely dangerous.
This type of fire suppression is considered a green option and does have many advantages used in the right application.
IG55 fire suppression agent is a blend of 50% Argon & 50% Blend of Nitrogen. The fire suppression gas is blended to offer better buoyancy for the fire suppression agent keeping the fire suppression gas at higher levels in the protected enclosure for longer!
Parameters
No. | Specification | IG55(50% nitrogen;50% argon) | |||
1 | Capacity | 80Ltr | 140ltr | ||
2 | Working Pressure | 20MPa | 30MPa | 20MPa | 30MPa |
3 | Device Model | QMH20/80 | QMH30/80 | QMH20/140 | QMH30/140 |
4 | Filling Capacity of Gas | 22.32kg | 33.48kg | 42kg | 58.2kg |
5 | Outside Diameter of Cylinder | Φ279mm | Φ267mm | Φ406mm | Φ356mm |
6 | Height of Cylinder | 1710mm | 1870mm | 1460mm | 1925mm |
7 | Filling Rate | 0.299kg/L | 0.415kg/L | 0.300kg/L | 0.201kg/L |
8 | Spraying Time | ≤120s | |||
9 | Power | DC24V/1.6A | |||
10 | Nitrogen Pressure of Driving Device | 6.0±1.0MPa(20℃) | |||
11 | Condition of Reserving Room for Container | temperature: 0~50℃ |
Features and benefits
Application
Package
We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.