Cylinder For Insulated FM200 Fire Suppression System Without Pollution In Data Center
Description
The table shows the specific parameters of several conventional bottles of different sizes
Cylinder 40L 70L 90L 100L 120L 150L 180L | |||||||
Nominal volume(L) | 40 | 70 | 90 | 100 | 120 | 150 | 180 |
Actual volume(L) | 40.5 | 70.5 | 90.5 | 100.5 | 120.6 | 150.5 | 180.6 |
Internal diameter(mm) | 300 | 350 | 350 | 350 | 350 | 400 | 400 |
Total length(mm) (including valve) | 890 | 1060 | 1265 | 1385 | 1578 | 1530 | 1773 |
Filling medium | FM200+nitrogen | ||||||
Weight of cylinder(kg) (including valve)
| 38 | 63 | 74 | 80 | 94 | 116 | 133 |
Test of hydraulic pressure | 8.4MPa | ||||||
Test of sealing pressure | 5.6MPa |
Components
The bottle part is composed of steel cylinder and cylinder valve
Application
As its name says, the single zone pipe network fm200 fire suppression system is suitable for a single protected zone, whose volume should be less than 3600 cubic meters as well as proportion should be less than 800 square meters. Because of its property and principles of putting off fire, the single zone pipe network fm200 fire suppression system can be used to protect some large and also significant places, such as the followings:
- Computer rooms
- Telecommunication center
- Facilities underground
- Offshore oil extraction
- Library
- Data and paper archives
- Valuable article storage
- Power generator storage room
Package
We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.