Insulated Inert Gas Inergen IG541 Fire Extinguishing System Without Residue
Characteristics of IG541 mixture gas fire extinguishing agent:
Parameters
No. | Specification | Technical Parameter | |
1 | Working Pressure | 20MPa | 30MPa |
2 | Device Model | QMH20/80 | QMH30/80 |
3 | Capacity | 80Ltr | 80Ltr |
4 | Filling Capacity of Gas | 23.9kg | 33.2kg |
5 | Outside Diameter of Cylinder | Φ286mm | Φ286mm |
6 | Height of Cylinder | 1910mm | 1910mm |
7 | Spraying Time | ≤120s | ≤120s |
8 | Filling Rate | 0.299kg/L | 0.415kg/L |
9 | Power | DC24V/1.6A | DC24V/1.6A |
10 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | 6.0±1.0Mpa(20℃) |
11 | Condition of Reserving Room for Container | temperature: -20~50℃ | temperature: -20~50℃ |
12 | Max Working Pressure | 23.2MPa | 36.6MPa |
13 | Min Working Pressure | 18MPa | 27MPa |
Features and benefits
Application
Electronic computer room, a data processing center, telecommunications facilities, process control, expensive medical equipment, industrial equipment, library, museum and art gallery, clean room, anechoic chamber, emergency power facilities, flammable liquid storage area, etc.
The place where the fire is easy to happen, like paint-spraying production line, aging-electrical equipment, rolling machine, printing machine, oil switch, oil immersed transformer, melt impregnating tank, tank, large generators, drying equipment, cement pro duction process of pulverized coal, and the ship's engine room, cargo hold, etc.
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.