Inert Gas Nitrogen IG100 Fire Extinguishing System Without Pollution For Anechoic Chamber
Inert gas fire extinguishing systems are the safe, natural way to extinguish a fire. Because of its unique patented valve assembly, the agent enters the protected zone within the industry required 60 seconds but at a steady flow rate — preventing destructive turbulence from occurring. This constant flow rate allows for the use of small-diameter, low pressure (and less expensive) piping from the inert gas container all the way to the nozzle. And, the necessary venting area is much smaller, which can reduce installation costs by as much as 60% on venting hardware.
Parameters
No. | Specification | Technical Parameter | |
1 | Working Pressure | 20MPa | 30MPa |
2 | Device Model | QMD20/80 | QMD30/80 |
3 | Capacity | 80Ltr | 80Ltr |
4 | Filling Capacity of Gas | 20kg | 24.68kg |
5 | Outside Diameter of Cylinder | Φ267mm | Φ267mm |
6 | Height of Cylinder | 1910mm | 1770mm |
7 | Spraying Time | ≤120s | ≤120s |
8 | Max Filling Rate | 0.25kg/L | 0.309kg/L |
9 | Power | DC24V/1.6A | DC24V/1.6A |
10 | Nitrogen Pressure of Driving Device | 6.0±1.0MPa(20℃) | 6.0±1.0MPa(20℃) |
11 | Condition of Reserving Room for Container | temperature: 0~50℃ | temperature: 0~50℃ |
12 | Max Working Pressure | 23.2MPa | 36.6MPa |
13 | Min Working Pressure | 18MPa | 27MPa |
Application
• Computer room, communication room, power distribution room, library, archives,
Museum, etc.
• Be used for electrical fire, liquid fire, solid fire, gas fire which can be cut off the gas
source before extinguishing occur, etc.
Advantages
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.