Enclosed Flooding Inert Gas Argonite IG55 Fire Extinguishing System Without Pollution
Decription
IG-55 is a clean agent fire extinguishing system using an inert gas (IG-55) consisting of 50% Nitrogen and 50% Argon and is used in total flooding systems. It has become widely accepted as the best performing, cost effective, and environmentally friendly inert gas fire extinguishing agent, offering extended hold times and great flexibility in design. IG55 fire suppression system utilises a superior valve design to automatically regulate the pressure of the extinguishant at discharge, providing an ideal discharge pressure and maintaining a constant flow rate throughout the discharge.
Parameters
No. | Specification | IG55(50% nitrogen;50% argon) | |||
1 | Capacity | 80Ltr | 140ltr | ||
2 | Working Pressure | 20MPa | 30MPa | 20MPa | 30MPa |
3 | Device Model | QMH20/80 | QMH30/80 | QMH20/140 | QMH30/140 |
4 | Filling Capacity of Gas | 22.32kg | 33.48kg | 42kg | 58.2kg |
5 | Outside Diameter of Cylinder | Φ279mm | Φ267mm | Φ406mm | Φ356mm |
6 | Height of Cylinder | 1710mm | 1870mm | 1460mm | 1925mm |
7 | Filling Rate | 0.299kg/L | 0.415kg/L | 0.300kg/L | 0.201kg/L |
8 | Spraying Time | ≤120s | |||
9 | Power | DC24V/1.6A | |||
10 | Nitrogen Pressure of Driving Device | 6.0±1.0MPa(20℃) | |||
11 | Condition of Reserving Room for Container | temperature: 0~50℃ |
System Composition
• Storage cylinder group, storage cylinder group frame, nitrogen driving device, nitrogen driving device frame,
the cylinder valve, liquid flow check valve, air flow check valve, electromagnetic starter, gas conveying pipeline, collecting pipe, choice valve, three links, reducer tee, reduceing elbow, flange, safety valve, pressure transmitter, pipe, nozzle, chemicals, fire detector, fire controller, sound and light alarm, alarm bell, gas light, emergency start / stop button, etc.
Application
Computer room, telecommunication room, transformer room, electrical switch and distribution room, generator room, leaching tank, drying equipment, paint spraying booth, electrical instrument room, control center, library, archives, treasure trove of cultural relics, etc.
Advantages
1. Compared with the traditional 15MPa system, the 30MPa system saves 25%-50% of the quantity of extinguisher cylinders.
2. It effectively reduces the floor area between the cylinders and improves the overall use value and utilization rate of the building.
3. Constant low pressure release of 6MPa reduces the cost of piping and components for the whole system.
4. The constant release pressure of 6MPa provides a more durable and effective pressure, with a transmission distance of up to 200 meters.
5. Whole system release by low pressure, it will be less impact on site personnel, equipment and building structure, and it will be more safety.
6. The external constant pressure-relief device only bears the pressure when the system is discharged, which is convenient for disassembly and maintenance, and effectively reduces the system failure rate.
7. After discharging, the system can be put into operation quickly with simple disassembly and secondary filling witn agent without replacing any parts.
8. It reduces the area of opening hole of gas pressure relief port, directly reduces the input cost of safety pressure relief device, and installs and arranges safety buckle become more simply.
9. IG55 fire extinguishing system can be widely used in important places that need rapid response to fire. There are workers, sudden fires and sensitive to chemical reactions on the site of the protection zone, the fire extinguishing system can effectively protect the safety of personnel and property.
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.