Cylinder for insulated Inert Gas Inergen IG541 Fire Extinguishing System without pollution
Characteristics of IG541 mixture gas fire extinguishing agent:
Parameters
No. | Specification | IG541(52% nitrogen;40% argon,8carbon dioxide) | |||
1 | Capacity | 80Ltr | 140ltr | ||
2 | Working Pressure | 20MPa | 30MPa | 20MPa | 30MPa |
3 | Device Model | QMH20/80 | QMH30/80 | QMH20/140 | QMH30/140 |
4 | Filling Capacity of Gas | 22.37kg | 33.56kg | 42kg | 58.2kg |
5 | Outside Diameter of Cylinder | Φ279mm | Φ267mm | Φ406mm | Φ356mm |
6 | Height of Cylinder | 1710mm | 1870mm | 1460mm | 1925mm |
7 | Filling Rate | 0.299kg/L | 0.415kg/L | 0.300kg/L | 0.201kg/L |
8 | Spraying Time | ≤120s | |||
9 | Power | DC24V/1.6A | |||
10 | Nitrogen Pressure of Driving Device | 6.0±1.0MPa(20℃) | |||
11 | Condition of Reserving Room for Container | temperature: 0~50℃ |
Features and benefits
Application
Computer room, telecommunication room, transformer room, electrical switch and distribution room,
generator room, leaching tank, drying equipment, paint spraying booth, electrical instrument room,
control center, library, archives, treasure trove of cultural relics, etc.
Package
We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.