Fuel Less Silent Type Standby Diesel Generator 1000kva 800kw Three Phase Genset Diesel Generator
Product Description
Brand: Cummins
40-50C°Cabinet temperature Water Tank Heat Sink, Belt
Driving Cooling Fan with Security Shield
24V Battery Charging Generator
Alternator Brand: ACEPOW
Single Bearing Alternator
Protection Grade: IP23 Insulation Grade: H
Shock Absorber
Dry Type Air Filter, Fuel Filter, Lube Filter
Generator Output Breaker: ZHENGTAI
Standard Control Module: HGM6120/ ACEPOW 6120
2 Starting Battery(24V) and Battery Connection cables
1 Exhaust Elbow Pipe,1 Waviness Shock Absorber Pipe,1 Flange, 1 Silencer
Technical documents
Genset Model | APC-1000 | ||
Prime Power (kw/kva) | 800/1000 | Standby Power(kw/kva) | 880/1100 |
Voltage (v) | 400/230 | Rated Speed (rpm) | 1500 |
Frequency (Hz) | 50 | Rated Current (A) | 1443 |
Connection: | 3 phase 4 wire | Power Factor: | 0.8 |
Engine Model: | KTA38-G4 | Alternator Model: | LVI634E |
Net Weight (kgs)-Open | 8250 | Net Weight (kgs)-Silent | 13000 |
Dimensions (mm)-Open | 4400*1800*2300 | Dimensions (mm)-Silent | 5500*2060*2900 |
Voltage Available: 50Hz: 380-400-415V/220-230-240V; 60Hz: 220-380-416-440-480V/110-208-220-240V
Any special voltage is also available as client’s request
Prime Power: comply with GB/T2820-97(eqv.ISO8528). Genset can run unlimitedly under certain power range. One hour 10% over load in every 12 running hours is allowed;
Standby Power: standby power is the limit value of maximum output for emergency use. It is off-oil power, overloading is prohibited
Engine Parameter: | |
Manufacturer/Model: Air Intake System: Fuel System: Cylinder numbers Displacement: Bore x Stroke Compression Ratio: Max. Power: Governing System: | CCEC, Cummins, KTA38-G4, 4 stroke PT Fuel Pump, EFC electronic governor 12 cylinders in “V” 37.8L 159 x 159 mm 13.9 : 1 970KW / 1319HP Electronic |
Exhaust System | |
Exhaust Volume: Exhaust temperature: Max. Allowed Back Pressure: | 3306 L/s 513 ℃ 10 KPa |
Intake System | |
Max. Allowed Pressure: Consumption: Air Flow: | 6.23 kPa 1213 L/s 30425 L/s |
Fuel System | |
100% Load (Prime): 75% Load(Prime): 50% Load (Prime): 100% Loding(Prime) | 202 g/Kw.h 207 g/Kw.h 218 g/Kw.h 187 L/h |
Lube System | |
Oil Capacity: Oil Consumption: Engine Oil Tank Capacity: Oil Pressure at rated speed: | 135 L ≦4g/kw.h 114L 310-448 kPa |
Cooling system | |
Coolant Capacity: Thermostat: Max. Water Temperature: | 258 L 82-93℃ 104℃ |
Q1: Are you a trading company or manufacturer?
A: We are more 50 years experience diesel generator manufacturer in China.
Q2: What is the power range of your diesel generator?
A: Our diesel generator power ranges from 5KVA-2000KVA.
Q3: How could I trust you?
A: During production and aseembling, we would like to provide all progress of pictures, videos, testing report, then we invite you to come to visit our factory and production workshop to witness a load test and see the professional operation we have to go on here.
Q4: What's the frequency of diesel generators?
A: 50/60HZ.
Q5: What's the voltage of your diesel generator?
A: 220/110V, 380/220V, 400/230V, 415/240V, 440/260V, 460/270V, and double voltage or high voltage.