Introduction Of 4-73 blower fan
G4-73/Y4-73 Centrifugal Fan/Induced Draft Fans are primarily applicable to steam boilers with capacity of 2-670t/h in power plants for air ventilation and inducing. If no special requirements, G4-73 blowers also apply to mining ventilation and general-purpose.
The medium for G4-73 ventilation fans should be air of no more than 80℃; the medium for Y4-73 induced draft fans can be smoke of no more than 250℃.
A dust removal device has to be added before the induced draft fans to minimize the dust content in the fans. The efficiency of dust removal devices should be no less than 85% according to the requirements of general power plants.
Product structures:
1. Impeller — It consists of 12 backward curved airfoil beveling blades welded between arc cone front disc and flat plate back disc. The airfoil blades ensure blowers’ high efficiency, low noise and high strength. All impellers pass static and dynamic balance correction and over-speed running test, so they enjoy stable and reliable operation. Impellers of ventilation fans and induced draft fans with same model No. apply the same structure different raw materials (generally speaking, A3 for ventilation fans and 16Mn for induced draft fans).
2. Casing-It is welded into a volute shape with common steel plates. Casings for single inlet blowers can be made into three different types (Casings for Blower №8~№12 can be made into an integrated non-separable structure; casings for blowers №14~№16 can be divided into two parts while casings for blowers №18~№29.5 can be divided into three parts). For induced draft fans, volute plates are appropriately thickened to prevent wearing from dust.
3. Inlet — To be integrated into a convergent streamlined structure and fixed onto the suction side of the blower with screws.
4. Air damper- The air damper is used to adjust the capacity of blower and radially installed before the air inlet. The adjusting range is from 0° (fully open) to 90° (fully closed). Looking from the side of the air inlet, the handle of the air damper is on the right side. For right rotation blowers, the handle moves from fully closed to fully open by moving from bottom to top. For left rotation blowers, the handle moves from fully closed to fully open by moving from top to bottom.
5. Driving unit — The main shaft of the driving unit is made of quality steel. Rolling bearing are used for this blower series. There are two kinds of bearing boxes: blowers with №8~16 apply integrated cyclone-type bearing boxes while blowers with №18~29.5 apply two separate pillow block bearing boxes. Bearing boxes for Y4-73 induced draft fans are equipped with thermometer and oil level indicator. The bearing box uses 30# motor oil. The oil amount to be added shall be based on the oil level indicator. If using grease lubrication, integrated cyclone-type bearing boxes for blowers with №8~16 should add an oil baffle plate on the side of rolling balls inside the bearing box and the slot for fixing the oil baffle plate is already reserved. Y4-73 induced draft fans are equipped with water-cooling devices. Therefore, a water pipe has to be added and the water consumption varies with ambient temperature and is usually considered as 0.5-1m3/h.
Technical data
Model No | G4-73 8A~29.5D |
Use | Smoke and dust removal |
Voltage | 380V/400V/415V/440V/450V/660V/1140V |
Color | Blue/Red/White/Grey/Yellow/Customized |
Application Industries | Steel Mill/Textile, Chemical, Smelting, Petroleum, and Kiln, and Many Factories |
Specification | Can provide according to customers' requirements |
Brand Name | SIMO |
Power | 18.5~1600KW |
Rotating Speed | 1450~730rpm |
Total Pressure | 2104~7218Pa |
Airflow | 16156~810000M3/h |
Package | Wooden Box/Steel frame |
Temperature Resistance | -40~350 Degrees |
Material | SS304,SS316 and Q235 |
Frequency | 50Hz/60Hz |
Impeller Type | Backward/Forward/Radial Blade |
After-Sales Service | Field Installation, Commissioning, and Training |
Efficiency(%) | Over 90% |
Exported to | All Countries |
Warranty | 18 Months |
FAQ
1. What parameters need to be provided when you design the Heat Dissipation Power Plant Blower Fan?
Answers: Air flow, total pressure or static pressure, inlet temperature, local voltage and frequency, Altitude etc.
If there is flammable and explosive gas, or big dust loading in the medium, please also inform the designer.
2. How about your company’s pre-sales service and after-sales service?
Answers: Before our cooperation, we have the professional technical team to help you make the technical solution according to your working condition, to make sure the centrifugal fan efficiency operation.
After sales service, we will offer 12 months’ repairing service, and provide lifelong follow-up services. Besides, our engineers are available for going abroad to offer the repairing service.
3. Does your company have qualifications?
Answers: SIMO Blower has obtained ISO 9001-2008, CE, TUV certifications and so on.
company introduction
Xinxiang SIMO Blower Co., Ltd., formerly known as Xinxiang Blower Factory, was established in 1955, which is the designated factory for fan production by the former Ministry of Machinery Industry. In 2006, the state-owned enterprise was restructed. In August 2008, the company was registered as Xinxiang SIMO Blower Limited Company, with a registered capital of RMB32,000,000. In June 2016, the company was renamed as Xinxiang SIMO Blower Co., Ltd. In May 2018, the national SME share transfer system was listed. It is one of the larger fan manufacturers in central China and a member unit of China Fan Association. SIMO Blower is a state-level high-tech enterprise, safety production standardization of level3 enterprise, a provincial level1 advanced management enterprise, and has won more than 20 provincial and municipal honorary titles such as "contract-honoring & trustworthy enterprise", "advanced quality management unit", and "customer satisfied enterprises". The company has passed the national level industrialization and information integration management system assessment, ISO9001 quality management system certification, ISO14001 environmental management system certification, OHSAS45001 occupational health and safety management system certification and CE certification.