One - Way Air Flow Compact Cleanroom HEPA Filter For Purification Equipment:
One-way flow ( laminar flow ) air supply, mostly usedfor purification equipment.
Wind speed 0.36 - 0.54 m / s.
Generally choose gel seal form.
Material and Application:
Frame: Aluminum
Media: EVA
Fiber Media: Glass Fiber
Gasket: PU gel / PU foam seal / CR seal strip
Operation Conditions: ≤ 80 % / 100 % RH, 40 ℃ / 80 ℃
Standard Size and Parameter:
Model
| Overall size L×W×D |
Rated Air velocity (m/s) |
Rated Airflow (m3/h) |
Initial Resistance (Pa) |
End resistance (Pa) |
Efficiency @MPPS |
YWGB610.610-93H14 | 610×610×93 | 0.45 | 600 | 110 | 250 | 99.995%≤E |
YWGB800.600-93H14 | 800×600×93 | 800 | ||||
YWGB1220.610-93H14 | 1220×610×93 | 1200 | ||||
YWGB1220.1220-93H14 | 1220×1220×93 | 2400 | ||||
WGB1170.570-90H14 | 1170×570×90 | 1100 | ||||
WGB1170.870-90H14 | 1170×870×90 | 1700 | ||||
WGB1170.570-70H14 | 1170×570×70 | 1100 | ||||
WGB1170.870-70H14 | 1170×870×70 | 1700 | ||||
WGB1170.1170-70H14 | 1170×1170×70 | 2200 |
Can the air filter be cleaned?
The air filter cleaning mentioned by the customer is generally aimed at the primary and medium efficiency air filter,
not the high efficiency air filter.
The main reasons are poor air quality, short service life of the air filter and high operating cost;
Filter cleaning is not recommended;
After cleaning, the static electricity completely disappears and the filtration efficiency is low;
During the cleaning process, the filter material structure will change and the filtration efficiency will be reduced;
After cleaning, particulate matter remains on the air inlet and outlet surfaces, increasing the load of the post air filter;
If the air filter is damaged during cleaning, especially if it is invisible to the naked eye, it will cause leakage and
affect the post air filter.