Specifications
MOQ :
1pcs
Price :
Negotiable
Payment Terms :
T/T, Western Union, L/C, MoneyGram
Supply Ability :
500pcs per month
Delivery Time :
10 working days after received your payment
Packaging Details :
Wooden Case
Cooling capacity(KW) :
101-316
Input power(KW) :
34.6-98.9
Power supply :
380v-50hz-3ph
Refrigeration :
R407C
Heating capacity(KW) :
111-337
Certificate :
CE
Mount type :
free standing
Chilled water flow(m³/h) :
17.4-54.3
Description

OEM Big Air Cooled Chiller Unit Industrial Air Coolers 111 KW - 337 KW

Model HLWH~

100SM

150SM

195SM

230SM

270SM

290SM

320SM

100SHM

150SHM

195SHM

230SHM

270SHM

290SHM

320SHM

Rated Cooling

Capacity

Cooling

Capacity (KW)

101

147

196

232

268

293

316

Comp.

Input Power (KW)

34.6

48.2

63.8

70.5

82.4

90.2

98.9

Rated Heating

Capacity

Heating

Capacity (KW)

111

159

212

245

284

311

337

Comp.

Input Power (KW)

34.1

47.4

62.8

69.2

80.8

88.4

97.2

Refrigerant

R407C

Power Supply

3φ-380V/50HZ

Safety Protection

Phase reversion protection,

Phase lack protection,

Overload current protection,
Discharge air temp. protection,

Low & High pressure protection,

Low temp. protection,

Water flow protection.

Number of

Refrigeration Circuit

1

Capacity Control (%)

0, 50, 75, 100

Refrigerant Charge (Kg)

30

42

56

68

78

84

93

Air Cooled

Heat Exchanger

Ripple Aluminum Fins Around Copper Pipe

Water Cooled

Heat Exchanger

Dia.of Pipe (inch)

2-1/2"

3"

3"

3"

4"

4"

4"

Water Side

Max Pressure (MPa)

1

Chilled

Water Flow(m3/h)

17.4

25.3

33.7

39.9

46.1

50.4

54.3

Water

Pressure Drop (kPa)

28

33

48

55

61

64

66

Flow of

Hot Water(m3/h)

19.1

27.3

36.5

42.1

48.8

53.5

58.0

Axial Fan

Air Flow

×1000m3/h

56.8

80.4

113.6

115.2

115.2

160.8

160.8

Power×Qty (KW)

1.2×4

2.0×4

1.2×8

1.2×8

1.2×8

2.0×8

2.0×8

Running Noise dB(A)

75

75

75

75

75

75

75

Total Weight (Kg)

1550

1960

2940

3120

3300

3480

3660

Running Weight(Kg)

1660

2140

3160

3340

3550

3730

3980

Note :

1. Rated Cooling Capacity Based on: DB Temperature 35℃/WB Temperature 24℃

Chilled water inlet/outlet temp. 12℃/7℃, Fouling factor: 0.088㎡.°C/KW.

2. Rated Cooling Capacity Based on: DB Temperature 7℃/WB Temperature 6℃

Hot water inlet/outlet temp. 40℃/45℃; Hot water range: 45℃~45℃;

2. Chilled Water Range: 5~20℃; Lowest Ambient Temperature: -5℃~43℃;

3. Heat recovery unit water in/out temperature: 50℃/55℃;

4.Changes of Specification for lmprovement May Be made without Notice.

Feature:

  1. Cooling capacity : 101 KW -316 KW , Heating capacity : 111-337
  2. Input power : 3P-380V-50Hz, Allowable fluctuate voltage: ± 10 % , allowable voltage difference in phase
  3. : ±2 % .

  1. Use PLC microcomputer control from famous LCD touch screen company , both English and
  2. Chinese human-machine interface.

4) Air cooled type , no cooling tower needed

  1. Accept orders for special requirements .

Services :

1 . Golden can supply OEM service for customers


2 . Produce heat pump according to customer's special demands


3 . Supply spare parts according to order quantity


4 . General testing and operational test carried out for every unit before delivery


5 . Long warranty period

Send your message to this supplier
Send Now

OEM Big Air Cooled Chiller Unit Industrial Air Coolers 111 KW - 337 KW

Ask Latest Price
MOQ :
1pcs
Price :
Negotiable
Payment Terms :
T/T, Western Union, L/C, MoneyGram
Supply Ability :
500pcs per month
Delivery Time :
10 working days after received your payment
Packaging Details :
Wooden Case
Contact Supplier
OEM Big Air Cooled Chiller Unit Industrial Air Coolers 111 KW - 337 KW

Pultruded FRP Online Market

Verified Supplier
11 Years
beijing, beijing
Total Annual :
>lessthan$1,000,000
Employee Number :
100~200
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement