Cold Weather Floor Heating Air Source Heat Pump High Temperature Equipment
Advantages
- Floor heating is heating from feet which is the cold part of body. It heats the room evenly at the same time, the temperature fluctuation is small,
- No direct blow on body, which is comfortable and not dry.
- Air Source heat pump could produces up to 50C hot water in the system, fast heating and constant heating.
- Indoor temeprature could be 20C , warm as the summer
- Air source heat pump is a automatic micro-computer controlled syste, equipted with completed protective devices against over voltage, over load, temeprature, flow etc.
- It use less than 30% electricity as power, more than 70% heat are absorbed from the air. Air source heat pumps are very energy-saving
Yushen air source heat pump
- Jet Boost compressor, high efficient and environmental-friendly, even in -25C can work in high COP
- Fan of heat exchanger is big diameter Jagged type, which increase the air flow tangent length when air going through fans, reduce noise; When the air volume is increased, the heat exchanger is more evenly.
- Multi-throttle channel design is accurate.Multiple energy-saving devices in a single system, precise control of refrigerant flow, enabling the unit to maximize heat/cooling capacity and maximum energy efficiency in various working environments, reducing operating costs
- The water side shell and tube heat exchanger have high efficiency and reliability.The industry's leading refrigerant distribution technology can effectively improve the uniformity of gas-liquid two-phase fluid distribution into heat transfer tubes, improve the utilization of heat exchange tubes, and achieve efficient heat transfer.
- Large-area hydrophilic aluminum heat exchangers increase the heat production.The four-row tube V-shaped arrangement has high heat exchange efficiency and uniform wind speed distribution.
- It adopts 9.52*0.35 internal thread high-efficiency heat exchange copper tube and 3.1mm large-format hydrophilic aluminum fins with better hydrophobicity; it improves the operating efficiency during frosting and reduces the number of defrosting.The optimized long flow path design and wide expansion of the expansion throttle ensure uniform distribution of refrigerant in low temperature environments. Ensure even frosting, complete defrosting, strong heating and efficient operation
Model data
Heating modelcode name.pdf
Model |
SDNA-075Y |
SDNA-090YB |
Compressor capacity |
25HP |
30HP |
Function |
Heat |
Heat |
Electricity |
380V 3N-50Hz |
380V 3N-50Hz |
Working conditions |
℃ |
-25~+45 |
-25~+45 |
Data |
Heata |
Nominal capacity |
KW |
44.5 |
56.2 |
Input power |
KW |
18.3 |
23.4 |
COP |
/ |
2.4 |
2.4 |
Heating IPLV(H) |
2.7 |
2.7 |
A7W35c |
KW/COP |
75.0/4.2 |
90.0/4.2 |
A2W35 |
KW/COP |
62.5/3.20 |
79.0/3.20 |
A-7W35 |
KW/COP |
52.5/3.0 |
63.2/3.0 |
A-15W55 |
KW/COP |
45.5 /1.97 |
56.2/1.97 |
A-20W45 |
KW/COP |
37.4/2.04 |
47.2/2.04 |
Max. running currency |
A |
56 |
70 |
Compressor quantity |
set |
2 |
4 |
Refrigerant/charging quantity kg |
/ |
R22/10*2 |
R22/5*4 |
Air blow type |
/ |
Top |
Top |
Water pipe diameter |
mm |
50 |
50 |
Rating flow |
m³/h |
12.6 |
12.6 |
Water side pressure loss |
kPa |
≤45 |
≤45 |
Noise level |
dB(A) |
62 |
62 |
Overall dimensions(L×W×H) |
mm |
2100×1100×2080 |
2100×1100×2080 |
Weight |
kg |
730 |
830 |
Nominal heating conditions:ambient dry bulb temperature 7℃, web bulb temperature 6℃, water inlet temperature 9℃,water outlet temperature 55℃
Applications
1. Publish bath center, Spa center
2. Hotel, school, hospital
3. Factory,company