Powerful Heating And Air Conditioning Units / Home Use Central Air Heat Pump
Heating And Air Conditioning Units Features
- Quality reliable :Apply world famous compressor ,4-way valve,expansive valve,the performance is superiority and more stable .
- Energy-saving:The power consumption is only 25% of electric water heater or 50% of solar water heaters .
- Environmental protection :The heat from air,without any pollution ,belong to the green home appliance.
- Safety :water and electricity is completely separated ,prevent the leakage,dry,explosion poisoning and so on dangers,safe and reliable use.
- Comfortable:could be used for several different places at the same time,it would supply long time and enough comfort hot water.
- Convenient:small main unit,convenient for installing,ewater tank can be equipped flexibly ,meet the requirements of different clients .
- Simple :detached main unit apply built-in heat exchanger,water tank is not installed with copper pipe,the main unit and water tank is only required to be connected with water pipe,the simple installation,high applicability.
- Automatic operation :apply microcomputer controller,users can freely set according to the actual requirements .
- sphere of application: 2-10 people family water supply.
- shower and kitchen water supply
- water tank capacity: 100L, 200L, 300L, 400L. 500L.
- high effeciency
- energy safe
- powerful heating
- convenient put intelligent control system
Heating And Air Conditioning Units Information
- Air source heat pump is 40% energy-saving than that of electric AC unit in heating.
- high automation, easy operation
- Water circulate inside the system, safe and comfortable
- It could be connected with different enders, e.g. fan coil, radiator, floor heating, convenient and high-efficient
Heating And Air Conditioning Units Parameter
Model |
SDNA-075Ycode name.pdf |
Compressor capacity |
25HP |
Function |
Heat |
Electricity |
380V 3N-50Hz |
Working conditions |
℃ |
-25~+45 |
Data |
Heata |
Nominal capacity |
KW |
44.5 |
Input power |
KW |
18.3 |
COP |
/ |
2.4 |
Heating IPLV(H) |
2.7 |
A7W35c |
KW/COP |
75.0/4.2 |
A2W35 |
KW/COP |
62.5/3.20 |
A-7W35 |
KW/COP |
52.5/3.0 |
A-15W55 |
KW/COP |
45.5 /1.97 |
A-20W45 |
KW/COP |
37.4/2.04 |
Max. running currency |
A |
56 |
Compressor quantity |
set |
2 |
Refrigerant/charging quantity kg |
/ |
R22/10*2 |
Air blow type |
/ |
Top |
Water pipe diameter |
mm |
50 |
Rating flow |
m³/h |
12.6 |
Water side pressure loss |
kPa |
≤45 |
Noise level |
dB(A) |
62 |
Overall dimensions(L×W×H) |
mm |
2100×1100×2080 |
Weight |
kg |
730 |
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity
A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
Project Introduction
Location: E 117 N 36.6
Floor quantity: 7
Building area: 12050M2
System design: ultra low temperature air source heat pump+radiator
Quantity of air-source heat pump: 9 set
The office building area of this project is 13,744 square meters and the heating area is 12050 square meters.
The building has 9 floors, the exterior wall has no insulation, and the windows have a single layer of glass.
The air source heat pump system was officially put into use in 2017, and the entire heating season is stable and reliable and efficient.
According to the coal heating calculation previously used by the user, it can save 287 tons of raw coal, reduce SO2 emissions by about 4.9 tons, reduce CO2 emissions by 516 tons per month, reduce coal ash, and discharge coal slag by about 86 tons.