Specifications
Brand Name :
Dixell
Model Number :
XR60CX
Certification :
EAC
Place of Origin :
Italy / China
MOQ :
5 sets
Price :
negotiate
Payment Terms :
T/T
Supply Ability :
1000pcs per weeks
Delivery Time :
4-6 weeks
Packaging Details :
cartons
Function :
Temperature display,control and adjust
Screen display :
Red
Application :
Chiller,Freezer and other Cooling equipment
Name :
Dixell ditital controller
Sensor :
PTC
Power :
220V/110V
Description

XR60CX Dixell Digital Refrigeration Controllers,Digital Temperature Controller For Coldroom And Freezer

GENERAL DESCRIPTION
Model XR60CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on
medium or low temperature ventilated refrigerating units. It has three relay outputs to control
compressor, fan, and defrost, which can be either electrical or reverse cycle (hot gas). It is also
provided with three NTC or PTC probe inputs, the first one for temperature control, the second one,
to be located onto the evaporator, to control the defrost termination temperature and to managed the
fan, the third one, optional, to connect to the HOT KEY terminals to signal the condenser
temperature alarm or to display a temperature. The digital input can operate as fourth temperature
probe.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a
network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It
allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.
SPECIFICATIONS / MODELS
XR01CX XR02CX XR03CX XR04CX XR06CX
Dimension
32*74*50mm
32*74*60mm
Power supply
12,24V ac/dc (± 10%)
115,230V ac/dc (± 10%)
Temperature sensor
Coldroom Temp Probe NTC / PTC √ / optional √ / optional √ / optional √ / optional √ / optional
Defrost / Fan Probe NTC / PTC √ / optional √ / optional √ / optional √ / optional √ / optional
Function digital signal input
Outout
Load or compressor 20A / 8A 20A / 8A 20A / 8A 20A / 8A 20A / 8A
Defrost Shut down defrost Shut down defrost 8A 8A
Fan 8A
Light / Auxiliary output 8A
Others
Hot Key Programming key
Heating / Cooling Heating / Cooling Heating / Cooling Heating / Cooling Cooling Cooling

XR10CX XR20CX XR30CX XR40CX XR50CX XR60CX XR70CX
Dimension
32*74*60mm
Power supply
12,24V ac/dc (± 10%)
115,230V ac/dc (± 10%)
Display
3 digital tubes, minus sign,Decimal point,Output status minus sign
Temperature sensor
Coldroom Temp Probe NTC / PTC
Evaporator Probe NTC / PTC
second Evaporator Probe NTC / PTC
Condenser Probe NTC / PTC
Digital input/display probe
Alarm,Trigger Defrost,Auxiliary probe, door switch,Pressure switch Settable Settable Settable Settable Settable Settable Settable
Relay Outout
compressor 20A / 8A 20A / 8A 20A / 8A 20A / 8A 20A / 8A 20A / 8A/16A 20A / 8A/16A
Defrost 8A 8A 8A 8A/16A
Evaporator Fan 5A/8A 5A/16A
Light / Alarm output 8A 5A/8A 8A/16A
Others
Hot Key Programming key
Serial Interface MODBUS
DEFROST
Two defrost modes are available through the “td” parameter:
• td=EL → defrost through electrical heater (compressor OFF)
• td=in → hot gas defrost (compressor ON).
Other parameters are used to control the interval between defrost cycles (id) ), its maximum length (Md) and two defrost modes: timed or controlled by the evaporator’s probe. At the end of defrost dripping time is started, its length is set in the dt parameter. With dt=0 the dripping time is disabled
FANS
With FC parameter it can be selected the fans functioning:
• FC=cn → will switch ON and OFF with the compressor and not run during defrost
• FC=on → fans will run even if the compressor is off, and not run during defrost
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fd” parameter.
• FC=cy → fans will switch ON and OFF with the compressor and run during defrost
• FC=oY → fans will run continuously also during defrost.
An additional parameter “FS” provides the setting of temperature, detected by the evaporator probe, above which the fans are always OFF. This is used to make sure circulation of air only if his temperature is lower than set in “FS”
FANS AND DIGITAL INPUT
When the digital input is configured as door switch iF=do, fans and compressor status depends on the dC parameter value:
• dC=no → normal regulation;
• dC=Fn → fans OFF;
• dC=cP → compressor OFF;
• dC=Fc → compressor and fans OFF.
When rd=y, the regulation restart with door open alarm.
FRONT PANEL COMMANDS
XR60CX Dixell Temperature Controller For Coldroom Freezer Room

XR60CX Dixell Temperature Controller For Coldroom Freezer Room

HOW TO SEE THE SET POINT
1.Push and immediately release the SET key, the set point will be showed;
2.Push and immediately release the SET key or wait about 5s to return to normal visualisation.
HOW TO CHANGE THE SETPOINT
1.Push the SET key for more than 2 seconds to change the Set point value;
2.The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3.To change the Set value push the or arrows.
4.To memorise the new set point value push the SET key again or wait 10s.
HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual defrost will start
HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the SET+keys for 3s (“°C” or “°F” LED starts blinking).
2. Select the required parameter. Press the “SET” key to display its value
3. Use ↑ or ↓ to change its value.
4. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET+↑ or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
ALARM SIGNALLING
Mess. Cause Outputs
"P1" Room probe failure Compressor output according to “Cy” e “Cn”
"P2" Evaporator probe failure Defrost end is timed
"HA" Maximum temperature alarm Outputs unchanged
"LA" Minimum temperature alarm Outputs unchanged
“EA” External alarm Outputs unchanged
“CA” Serious external alarm All outputs OFF
“dA” Door Open Compressor and fans restarts
XR60CX Dixell Temperature Controller For Coldroom Freezer Room

Send your message to this supplier
Send Now

XR60CX Dixell Temperature Controller For Coldroom Freezer Room

Ask Latest Price
Brand Name :
Dixell
Model Number :
XR60CX
Certification :
EAC
Place of Origin :
Italy / China
MOQ :
5 sets
Price :
negotiate
Contact Supplier
XR60CX Dixell Temperature Controller For Coldroom Freezer Room
XR60CX Dixell Temperature Controller For Coldroom Freezer Room
XR60CX Dixell Temperature Controller For Coldroom Freezer Room
XR60CX Dixell Temperature Controller For Coldroom Freezer Room

Shenzhen Sino-Australia Refrigeration Equipment Co., Ltd.

Active Member
5 Years
shenzhen
Since 2003
Business Type :
Manufacturer, Distributor/Wholesaler, Agent, Importer, Exporter, Trading Company, Seller
Total Annual :
1500-1800
Employee Number :
150~160
Certification Level :
Active Member
Contact Supplier
Submit Requirement