Model meaning:
Z W 20 A - 12 / T - 0 0
Z: vacuum circuit breaker
W: Outdoors
20A: Design Number
12: Rated voltage (KV)
T: spring operating mechanism
0: Rated current (A)
0: Rated short-circuit breaking current (kA)
Environmental Conditions
1. Altitude: ≤1000m; if applied in special conditions, it is designed to 2000m to 4000m to meet the requirements of different altitudes.
2. Ambient temperature: -45℃~+40℃;
3. Wind speed≤35m/s;
4. It is placed in the places without violent vibration
Technical Parameters
No. | Item | Unit | Value |
1 | Rated voltage | kV | 12 |
2 | Rated frequency | Hz | 50 |
3 | Rated current | A | 630 |
4 | Rated short-circuit breaking current | kA | 20 |
5 | Rated peak withstand current (peak) | kA | 50 |
6 | Rated short-time withstand current/endurance | kA/s | 20/4 |
7 | Rated short-circuit making current (peak) | kA | 50 |
8 | Rated operating sequence | O-0.3s-CO-180s-CO | |
9 | Mechanical endurance | Time | 10000 |
10 | Rated short circuit breaking current breaking times | Time | 30 |
11 | Rated cable-charging breaking current | A | 25 |
12 | Power frequency withstand voltage(1min): Dry test (wet) phase-to-phase, to earth/fracture(wet test) | kV | 42(34)/48(36) |
13 | Lightning impulse withstand voltage(peak) phase-to-phase, to earth/fracture | kV | 75/85 |
14 | 1min power frequency withstand voltage of secondary circuit | kV | 2 |