Specifications
Brand Name :
Tianan Electric
Model Number :
ZBW3-40.5
Certification :
CQC
Place of Origin :
CHINA
MOQ :
1 unit
Payment Terms :
L/C, D/A, D/A, D/P, D/P, T/T, T/T, Western Union, MoneyGram
Supply Ability :
2000 Sets/year
Delivery Time :
45 work days
Packaging Details :
Nude
Price :
Pending
Capacity :
400 kVA-20000kVA
Rated HV :
40.5Kv
Environment :
Outdoor
Transformer :
Oil transformer
Rated Lv :
0.4KV/12KV
Tap Changer: :
Regulate The Output Voltage
Description

35kV High Voltage Prefabricated / Compact / Combined Transformer Substation

Service condition


1. Altitude: ≤ 1000m (above sea level)

Ambient temperature: Max. 40C Min. -25C
Max. Monthly average temperature: ≤ 35C

2. Max. Yearly average temperature: ≤ 25C

3. Relative humidity: Daily average value≤ 95%, monthly average value≤ 90%

4. Max. Daily difference in temperature: 25C

5. Sunlight intensity: 0.1W/CM2 (wind speed 0.5M/S);

6. Outdoor wind speed: ≤ 35m/s;

7. Pollution grade: Grade III;

8. Rain proof grade: Grade 3;

9. The gradient on installation spot shall as client's rebe not more than 3° ;

10. Ability of anti-earthquake: Horizontal acceleration of ground surface is 0.2g
Vertical acceleration of ground surface is 0.1g;

11. Installation spot: The spot should has no fire/explosion danger/serious pollution/chemical
corrosion
and exquisite shake.

Our advantage

1.Various special requirement from customer or typical specification .

2.Competitive price (Real

3.Good service and after sales.

4.In time delivery.

5. Manufacturing after drawings approved.

6.OEM is acceptable.We can change the design quirements.

3.Excellent quality control.

Unit Switch cubicle Circuit breaker Items In Data
H. V. unit 40.5kV KYN10-40.5
JYN1-40.5
ZN23-35
ZN12-35
LN2-35(Z)
Rated voltage kV 40.5
Rated current A 1250-1600
Rated short-circuit breaking current kV 20-31.5
Rated short-circuit making current
(crest)
A 50-80
On-load startingNAL36
NALF36
Rated current A 630
Rated short-time withstand current kA/s 25/2
L. V. unit 12kV XGN56-12
XGN2-12
KZN1-12
KYN1-12
ZN28A-12
ZN28B-12
VD4
VT2-12
VT1-12
Rated voltage kV 12
Rated current A 630-3150
Rated short-circuit breaking current(r. m. s) kA 16-50
Rated short-circuit making current
(crest)
kA 40-125
HXGN11-12
(F)
HXGN26-12 (F)
On-load starting
FN16-12
FN26-12
FN26-12R
Rated current A 630
Rated short-time withstand current kA/s 20/3, 25/2
0.4kV GGD
GCT
GCS
DW15
ME, M, F
DZ20
CM, H, S series
Rated current of circuit breaker A 70-3900
Breaking capability(400V) kA 28-80
Transformer unit SC9, S9, SZ9 transformer Rated voltage kV 40.5
Rated capability kVA 400-20000
Ratio kV / kV 35/10, 35/6.3, 35/0.4

Send your message to this supplier
Send Now

35kV High Voltage Prefabricated / Compact / Combined Transformer Substation

Ask Latest Price
Brand Name :
Tianan Electric
Model Number :
ZBW3-40.5
Certification :
CQC
Place of Origin :
CHINA
MOQ :
1 unit
Payment Terms :
L/C, D/A, D/A, D/P, D/P, T/T, T/T, Western Union, MoneyGram
Contact Supplier
35kV High Voltage  Prefabricated /  Compact  / Combined Transformer Substation
35kV High Voltage  Prefabricated /  Compact  / Combined Transformer Substation

Ningbo Tianan (Group) Co.,Ltd.

Verified Supplier
8 Years
zhejiang, ningbo
Since 1969
Business Type :
Manufacturer, Exporter, Trading Company, Seller
Total Annual :
250000000-300000000
Employee Number :
3000~3500
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement