Crane trolley line installation and acceptance standards and specifications
1. Bracket
2.Suspension parts: the position is correct, the installation is firm, and the quantity is compounded.
3.The main body of the trolley line
4.Retractor:
5. Bracket bracket
Single wire "H" type ≤ 1.5M below 300A, ≤ 3M above 400A.
Multi-line seamless sliding contact line type 1.0-1.5M.
Conduit type 1.0-1.5M.
Cable pulley type 1.0-2.0M.
The distance between arc section brackets should be <1.0M according to the site conditions.
6. Fasteners: fastening
The torque of the nut should meet the manufacturer's recommended value. Recommended value: M10-28NM, M8-12NM, M6-6.5NM VII. Collector
7. Power incoming line: The incoming line end is firm and must not bear tension.