Specifications
Brand Name :
Ningbo Suntech Power
Model Number :
FKTF-280kVA/35kV;140kV
Certification :
ISO9001
Place of Origin :
Ningbo,China
MOQ :
One Unit
Price :
Negotiable
Payment Terms :
T/T
Supply Ability :
10units/1months
Delivery Time :
25-30 Work Days
Packaging Details :
Export Standard Wooden Case With Fumigation Free
Test Principle :
Variable Frequency Resonant Circuit
Test Item :
AC Withstand Voltage Test Under 108KV
Max.capacity :
OEM
Max. Voltage :
OEM
Design Feature :
Portable Type
Test Frequency :
45-300Hz
Duty Cycle :
60 Mints
Test Object :
35KV Cable , 10KV Cable,110KV Cable
Test Standard :
IEC 60060-1:2010;IEC 62271-203:2011 For GIS, IEC 60840:2011 For XLPE Cable;
Power Supply :
380V±10%
Rated Voltage :
35kV;140kV;
High Light :
280kVA Series Resonant Test System, Frequency Modulation Type Resonant Test System, 35kV AC Resonant Test System
Description

Frequency modulation type series resonance test device

1.Applicable scope of device
1. Meet the AC withstand voltage test of 10kV/300mm2 cable, the capacitance per unit length is 0.3755μF/km, the cable length is 2000m, the capacitance of the tested cable is 0.75μF, the test voltage is 22kV, and the test time is 5min;
2. Meet the 35kV/240mm2 cable AC withstand voltage test, the capacitance per unit length is 0.175μF/km, the cable length is 1000m, the capacitance of the tested cable is 0.175μF, the test voltage is 52kV, and the test time is 180min;
3. Meet the AC withstand voltage test of 110kV/630mm2 cable, the capacitance per unit length is 0.1880μF/km, the cable length is 100m, the capacitance of the tested cable is 0.188μF, the test voltage is 128kV, and the test time is 60min;


2. The device follows the standard
GB10229-88 "Reactor"
GB50150-2016 "Power Equipment Handover Test Regulations"
DL/T 596-1996 "Preventive Test Regulations for Power Equipment"
GB1094.1-GB1094.6-96 "Enclosure protection grade"
GB2900 "Electrical Terminology"
GB/T16927.1~2-1997 "High Voltage Test Technology"
GB 191-2000 "Packaging, Storage and Transportation Graphical Signs"
JB/T 9641-1999 "Test Transformer"
IEC358(1990) "Coupling Capacitor and Capacitance Voltage Divider"
Q/WFK005-2005 "Test Transformer" Fanke Company Enterprise Standard
Q/WFK008-2004 "Test Reactor" Fanke Company Enterprise Standard


3. Environmental conditions of the device
1. Ambient temperature: -5℃-+45℃;
2. Relative humidity: ≤90﹪, no condensation;
3. Altitude: ≤1000m.


4.Fourth, the main technical performance requirements of the device
1. Rated capacity: 280kVA;
2. Rated voltage: 35kV; 140kV;
3. Rated current: 2A;
4. Power supply: 380V±10%;
5. Rated capacity of variable frequency power supply: 20kW;
6. Working frequency: 45-300Hz;
7. Frequency adjustment fineness: 0.01Hz; frequency instability: ≤0.01%;
8. Working time: 180min continuous operation is allowed under rated power;
9. Temperature rise: after rated continuous operation for 180 minutes, the temperature rise of each part of the device is ≤65K;
10. Output waveform: sine wave, waveform distortion rate <1%;
11. Quality factor: the device itself Q>30 (when f=40Hz);
12. Protection: with overcurrent, overvoltage and flashover protection (see the frequency conversion power supply section for details);
13. Measurement accuracy: 1.5 effective value.

Send your message to this supplier
Send Now

Frequency Modulation Type Resonant Test System 280kVA Series

Ask Latest Price
Brand Name :
Ningbo Suntech Power
Model Number :
FKTF-280kVA/35kV;140kV
Certification :
ISO9001
Place of Origin :
Ningbo,China
MOQ :
One Unit
Price :
Negotiable
Contact Supplier
Frequency Modulation Type Resonant Test System 280kVA Series

Ningbo Suntech Power Machinery Tools Co.,Ltd.

Verified Supplier
5 Years
zhejiang, ningbo
Since 1995
Business Type :
Manufacturer, Distributor/Wholesaler, Agent, Importer, Exporter, Trading Company, Seller, Other
Total Annual :
>300 Million
Employee Number :
>158
Certification Level :
Verified Supplier
Contact Supplier