100kw Diesel Generator 50Hz Water Cooling Dalian Deutz Soundproof Genset
1 . Powered by Genuine DEUTZ Water-cooling diesel engine .
2 . Brand New Stamford , Leroy somer , Marathon , AC atlernator
Ratings : 400/230V , 3Ph , 50Hz , 1500Rpm , 0.8PF , IP23 , H insulation class
3 . Standard CHINT or DELIXI circuit breaker . ( ABB breaker as optional )
4 . Steel base fuel tank with anti-vibration mounting .
5 . Based 8 hours build-in fuel tank ensure daliy use .
6 . muffler exhaust system , free-maintenance battery , user's manual .
7 . Flexible fuel lines and lube oil , fuel & water drain cocks .
8 . Deepsea , ComAp , Smartgen or other digital control module .
9 . Shrink wrap or wooden box packing method .
DEUTZ is one of the world’s leading manufacturers of innovative drive systems. Its core competences are
the development, production, distribution and servicing of diesel, gas and electric drivetrains for
professional applications. The engine specialist offers a broad product spectrum with capacities ranging
up to 620 kW that is used in construction equipment, agricultural machinery, material handling equipment,
stationary equipment, commercial vehicles, rail vehicles and other applications.
PRODUCT DESCRIPTION |
Genset Model | BS-D125 | ||
Prime Power (kw/kva) | 100 / 125 | Standby Power(kw/kva) | 110 / 137.5 |
Voltage (v) | 400 | Rated Speed (rpm) | 1500 |
Frequency (Hz) | 50 | Rated Current (A) | 180 |
Connection: | 3 phase | Power Factor: | 0.8 |
Engine Model: | BF4M1013FC | Alternator Model: | UCI274D |
Net Weight (kgs)-Silent | 1800 | Dimensions (mm)-Silent | 2900x1080x1970 |
Engine Parameter | |
Manufacturer/Model Engine type Fuel System Displacement Bore x Stroke Compression Ratio Max. Power Governing System | DEUTZ BF4M1013FC Single injection pumps 4.76 L 108 x 130 mm 18.1 : 1 129 KW Electronic. gov |
Exhaust System | |
Exhaust temperature Max. Allowed Back Pressure Exhaust Gas flow | 530℃ 30 mbar 1389m3/h |
Intake System | |
Max. intake depression (Switch setting) Combustion air volume | 25 mbar 482m3/h |
Fuel System | |
25% Load (Prime) 50% Load (Prime) 75% Load (Prime) 100% Load (Prime) | 7.6 liters / hr 14 liters / hr 20.9 liters / hr 28.9 liters / hr |
Lube System | |
Oil Capacity Oil Consumption (as % of fuel consumption) Min.Oil Pressure (warning) Min.Oil Pressure (shut down) Max.permissible oil temperature(oil pan) | 11 liters 0.3 2.7 bar 2 bar 130 ℃ |
Cooling system | |
Max.perm.coolant outlet temperature Max.temperature of coolant (warning) Max. temperature of coolant (shutdown) Temperature at which thermostat starts to open Temperature at which thermostat is fully open Temperature at CAC outlet at standard conditions Coolant capacity (engine) Coolant capacity (incl. cooling unit) Air to boil (max. permissible cool. air temp. at fan) Fan power consumption Cooling air flow Air pressure loss, external | 105℃ 108℃ 110℃ 83℃ 98℃ 40℃ 7.4 L 19.7L 55℃ 5 KW 9000 m3/h 1.5 mbar |
Alternator Parameter: Basic Information | |
The alternators meet the standards of: GB755, BS5000, VDE00530, NEMAMG1-22,IED34-1,CSA22.2 and AS1350 | |
Technical Data | |
Manufacturer Phases Bearing numbers Power Factor Protection Class Altitude Condition Excitation Insulation class/Temp. rise class Tel. Influence Factor TIF Tel. Harmonic Factor THF Steady State Voltage Regulation Alternator Capacity Efficiency | STAMFORD UCI274D 3 1 0.8 IP23 ≤1000M Brushless, self-excitation H / H <50 <2% ≤±1% 100KW 90.6% |
FAQ |
Q : What is the difference between Prime power and Standby power ?
A : Prime power is 12hours continous power , one hour 10% over load in every 12 running hours is allowed .
Standby power is the limit value of maximum output for emergency use . Overloading is prohibited
Q : How to choose the power ?
A : Collect all power of your equipments , take the current into your consideration .
Q:What is your MOQ?
A: Above 1pc
Q: Do you offer OEM service?
A: Yes
Q: What is your lead time?
A: About 30 days after receiving deposit or original L/C.But if your order with some special design,
then the delivery time is longer.
Q: What is your payment term?
A: 30% T/T in advance, the rest payment before shipment. Or irrevocable L/C.