Parameter
No. | MAIN TECHNICAL DATA | Unit | ||
1 | Rated Voltage | kV | 12 | |
2 | Lightning Impulse Withstand Voltage (Peak) | kV | 75 | |
3 | Short-time (1min) Power-frequency Withstand Voltage | kV | 42 | |
4 | Rated Frequency | Hz | 50/60 | |
5 | Rated Current | A | 630 | |
6 | Rated Short-time Withstand Current | kA | 6.3 | |
7 | Rated duration of Short-circuit | s | 4 | |
8 | Rated Breaking Current | A | ||
9 | Limiting Breaking Current | kA | ||
10 | Rated Making Current | kA | 6.3 | |
11 | Rated Operating Frequency | AC-3 | Operations/h | |
AC-4 | 300 | |||
12 | Short-time Operating Frequency | Operations/h | ||
13 | Utilization Category | AC | ||
14 | Electrical Endurance | AC-3 | Operations | 2.5*105 |
AC-4 | 5*104 | |||
15 | Mechanical Endurance | Operations | 3.0*105 | |
16 | Clearance Between Open Contacts | mm | 5.5~7 | |
17 | Contact Closing Force Due to Bellows and Atmosphere | N | 80±10 | |
18 | Counter force of Contacts at Full Stroke | N | 110±10 | |
19 | Circuit Resistance at Min. Rated Contact Force | μΩ | ≤ 160 | |
20 | Contact Limit Erosion | mm | 1.5 | |
21 | Mass of Moving Parts | kg | 0.49 | |
22 | Internal Gas Pressure | Pa | ≤ 1.33*10-3 | |
23 | Shelf Life | Year | 20 |