Green Color Cummins Diesel Generator KTA19-G4 400KW / 500KVA
Genset Specifications:
Genset model | SCF500A |
Genset rated power | 400KW / 500KVA |
Rated voltage | 400/230V (adjustable) |
Rated current | 720 Amps |
Frequency | 50 Hz |
Power factor | 0.8 Lagging |
Connecting type | 3 phase 4 wire |
Cooling system | Closed cycle water-cooled with fan, water tank |
Overall dimension (L×W×H) mm | 3300×1250×1850 |
Gross weight (kg) | 4670 |
Engine Specifications:
Diesel Engine | |
Brand | CUMMINS |
Model | KTA19-G4 |
Engine type | 6 cylinders in Line, 4 stroke, direct injection |
Aspiration | Turbocharged and air-to-air intercooled |
Rotating speed | 1500 RPM |
Engine cooling system | Water-cooled |
Speed governing system | Electronic speed governor |
Starting method | By 24V batteries |
Engine filter system | Dry type air filter ,fuel filter, oil filter, water filter |
Displacement(L) | 19 |
Bore×Stroke(mm) | 159×159 |
Compression ratio | 14.5:1 |
100% Load fuel consumption (l/h) | ≤96 |
Lube capacity(L) | 38 |
Alternator Specifications:
Alternator | |
Brand | FARADAY |
Model | FD5M1-4 |
Excite type | Brushless self-excited AVR regulation |
Connecting type | 3 phase 4 pole |
Steady frequency change | 0.50% |
No load voltage | ≥95%-105% |
Steady voltage | ≤±1% |
Insulation class | Class H |
Protection grade | IP23 |
Manufacturing Standards:
ISO8528; ISO1105; ISO3046; GB/T2820; GB755; BS5000; NEMAMG-22; YD/T502
Electrical Parameters
Wave distortion: <10%
Voltage fluctuation: <0.5%
Voltage / frequency fluctuation: <=0.5%
AVR self-regulated, voltage regulation rate: <=+- 1%
Radio interference restraining accords with stipulation of VDE0875-N and ISO8528
Control Function
Key start / auto start
Monitoring meters: Current; Frequency; Wire Voltage; Genset KVA; Genset KW; Output
Capacity; Output KW.H; Power Factor.
Warning/Shutdown: Alternator Under/Over Volts, Frequency; Under/Over Speed; Low Oil Pressure; High Engine Temp; High/Low Battery Volts; Over Current; Earth Fault Shutdown.
Voltage
Special Type Generator Set
1. Acoustic Enclosure Generator Set.
2. Containerized Generator Set.
3. Trailer-Mounted Generator Set.
4. Mobile Generator Set (Truck Mounted).