Specifications
Brand Name :
SHX
Model Number :
SCS990A
Certification :
ISO9001:2015, CE, TUV, BV
Place of Origin :
Foshan, China
MOQ :
1 Set
Price :
Negotiable
Payment Terms :
100% L/C at Sight, T/T
Supply Ability :
80 Sets per month
Delivery Time :
20 working days
Packaging Details :
Standard export packing
Product :
Open Type
Cooling method :
Water cooled
Speed governing :
Electronic
Starting method :
Electrical start by 24V batteries
Engine :
Cummins / Perkins / China brands
Alternator :
Stamford / Marathon / Faraday and China Brands
Control mode :
Manual/auto
Medium of cooling :
Air
Description

200Amp AC 3 Phase 50Hz Open Diesel Generator, Emergency Backup Generator

Genset Specifications:

Genset model SCS150
Genset rated power 110KW / 138KVA
Rated voltage 400/230V (adjustable)
Rated current 200Amps
Frequency 50 Hz
Power factor 0.8 Lagging
Connecting type 3 phase 4 wire
Cooling system Closed cycle water-cooled with fan, water tank
Overall dimension (L×W×H) mm 4100×1800×2500
Gross weight (kg) 7500
Diesel Engine
Brand CUMMINS (Optional )
Model 6BTAA5.9-G2
Engine type 4 cylinders in Line,4 stroke, direct injection
Aspiration Turbocharged and air-to-air aftercooled
Rotating speed 1500 RPM
Engine cooling system Water-cooled
Speed governing system Electronic speed governor
Starting method By 24V batteries
Engine filter system Dry type air filter ,fuel filter, oil filter, water filter
Displacement(L) 5.9
Bore×Stroke(mm) 102×120
Compression ratio 17.5: 1
100% Load fuel consumption (l/h) ≤208
Lube capacity(L) 16.4
Alternator
Brand STAMFORD (Optional )
Model UCI274E
Excite type Brushless self-excited AVR regulation
Connecting type 3 phase 4 pole
Steady frequency change 0.50%
No load voltage ≥95%-105%
Steady voltage ≤±1%
Insulation class Class H
Protection grade IP23

Control System

  • Control, monitor and protect the Generator Set including:
  • High water temperature
  • Low oil pressure
  • Over and under speed
  • Over current
  • Under/Over generator voltage
  • Start and stop failure
  • Low and high battery voltage
  • Charge fail
  • Emergency stop

INSPECTION AND TEST

1 GENERAL

1.1 Each engine shall be tested at manufacturer’s workshop to certify the engine output and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.

1.2 All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.

1.3 The purchaser shall call for additional testing if test results are unsatisfactory or marginal. Any equipment rejected shall be repaired or replaced to the purchaser’s satisfaction and tests shall be repeated.

1.4 Any unsatisfactory material, equipment, installation, or workmanship shall be replaced or repaired to the purchasers satisfaction at the manufacturers cost.

1.5 The engine and generator shall be tested individually in accordance with relevant standards specified above.

1.6 The completed and individually tested engine and generator shall be assembled onto the base plate with all auxiliaries, instruments and controls for a complete test of the generator set.

200Amp AC 3 Phase 50Hz Open Diesel Generator, Emergency Backup Generator

Send your message to this supplier
Send Now

200Amp AC 3 Phase 50Hz Open Diesel Generator, Emergency Backup Generator

Ask Latest Price
Brand Name :
SHX
Model Number :
SCS990A
Certification :
ISO9001:2015, CE, TUV, BV
Place of Origin :
Foshan, China
MOQ :
1 Set
Price :
Negotiable
Contact Supplier
200Amp AC 3 Phase 50Hz Open Diesel Generator, Emergency Backup Generator

Guangdong Sunkings Electric Co., Ltd

Active Member
7 Years
guangdong, foshan
Since 2000
Business Type :
Manufacturer, Exporter
Total Annual :
1500-2000
Employee Number :
50~100
Certification Level :
Active Member
Contact Supplier
Submit Requirement