Yokogawa EJX910A Multivariable Pressure Transmitter EJX EJA Series
The high performance EJX910A multivariable transmitter features multi-sensing technology with a single-crystal silicon resonant sensor that outputs the measured differential pressure, static pressure and process temperature, which covers multiple protocols: HART, FOUNDATION fieldbus and RS485 Modbus.
Additionally the HART protocol and FOUNDATION fieldbus protocol types are suitable to measure dynamically calculated and fully compensated mass flow for liquid, gas, or steam. 4 to 20 mA DC signal output is available in HART protocol type.
FDT/DTM* standard conforming software is available for transmitter configuration. FSA120 (FlowNavigator®) is used for flow configuration of the HART protocol and FOUNDATION fieldbus protocol types.
The EJX-A series is Yokogawa's premium performance line of DPharp transmitters. Released in 2004, it offers the performance and stability needed in demanding applications. The EJX-A series performance makes it the thoroughbred of the DPharp family of pressure transmitters.
The EJX910A multivariable transmitter is a remarkable innovation in multi-sensing technology. It makes optimal use of the unique characteristics of the DPharp sensor to give you greater insight into your process.
EJX910A features include:
Mass Flow Version:
Multi-Sensing Version:
Explore how the EJA910A can help you Boost your bottom line.
OpreX is the comprehensive brand for Yokogawa’s industrial automation (IA) and control business and stands for excellence in the related technology and solutions. It consists of categories and families under each category. This product belongs to the OpreX Field Instruments family that is aligned under the OpreX Measurement category.
item | value |
Warranty | 1 Year |
Customized support | OEM, ODM |
Place of Origin | Japan |
Brand Name | Yokogawa |
Model Number | EJX910A |
Style | S2 |
Supply | 10.5-42 V dc |
MWP | 25 MPa |
Output signal | 4~20mADC |
Protocol type | Hart/FOUNDATION Fieldbus /Modbus |
Burst Pressure Limits | 69 MPa (10000 psi) |
Display | LCD |
Ambient Temperature | –40 to 85°C (–40 to 185°F) |
Ambient Humidity | 0 to 100% RH |
Load | 0 to 1335Ω |