Dwyer 0-2kpa All Stainless Steel Pressure Gauge Digital Magnehelic Gauge
Introduction
Dwyer pointer differential pressure gauges can achieve 2% accuracy and up to 81 range options to meet the needs of a variety of applications. The tried-and-true magnetic linkage principle, using non-wear moving parts, can quickly indicate low pressure - positive pressure, negative pressure (vacuum) or differential pressure of air or non-corrosive gases. Its design is shockproof, shockproof and has the ability to withstand overpressure. It does not evaporate, freeze liquid differential pressure meter phenomenon, also does not cause poisoning or leveling problems.
Specification
item | value |
warranty | 1 year |
customized support | OEM,ODM |
Place of original | USA |
Brand name | Dwyer |
Model number | 2000 |
Accuracy | ±1% of FS |
Temperature Limits | 32 to 122°F |
Brand Name | dwyer |
Type | Digital Pressure Gauges |
Material | Stainless steel |
Pressure range | 0-2kpa |
Weight | 1.18 lb (535 g) |
Pressure Rating | 0-2kpa |
Model Number | series 2000 |
Working principle
Application: used for measuring positive and negative pressure difference; It is suitable for measuring positive and negative pressure difference of clean workshop in pharmaceutical factory and electronic factory, hVAC, purification table, spraying room, environmental protection dust removal equipment, air conditioning cabinet filter net pressure difference detection, etc.
Performance characteristic
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Housing Materials: Glass filled plastic.
Accuracy: ±1% FS including linearity, hysteresis and repeatability; ±2% FS for ranges 1 in w.c. and below.
Temperature Limits: 0 to 140°F (-18 to 60°C).
Compensated Temperature Limits: 32 to 122°F (0 to 50°C).
Long Term Stability: ±1% FS per year.
Thermal Effect: ±0.05% FS/°F typ.; ±0.10% FS/°F for ranges 1 in w.c. and below. Display: 4-digit LCD (digits: 0.60H x 0.33W). Display Update: Selectable for 1 second to 10 minutes or update only from button push.
Pressure Limits: Normal and bi-directional ranges 5 in w.c. and lower = 2 psi (13.7 kPa); Normal and bi-directional ranges 10 in w.c. and higher = 11 psi (75 KPa).
Selectable Engineering Units: in w.c., psi, kPa, Pa, mm w.c., mBar, in Hg, mm Hg, FS (0-100%).
Power Requirements: 9 V alkaline battery, included, user replaceable or external power supply 9-24 VDC.
Battery Service Life: Battery life depending on the display update setting: 150 hours (typical) if display update = 1 second; 9 month (typical) if display update = 10 minutes; 1.5 years (typical) if display update is disabled. Battery may last up to four times longer when using lithium-based battery ULTRALIFE U9VL-J.
Current Consumption: 5 mA max.
Electrical Connections: Removable terminal block for 16 to 26 AWG.
Electrical Entry: Cable gland for 0.114 to 0.250˝ (2.9 to 6.4 mm) diameter cable. Process Connections: 1/8˝ (3 mm) ID tubing.
Enclosure Rating: NEMA 4X (IP66).
Weight: 1.18 lb (535 g).
Size: 5˝ (127 mm) OD front face.
Agency Approvals: CE.
Application areas: