Honeywell Fema-Dps400 Adjustable Air Differential Pressure Switch 40-400Pa
applied range
Differential pressure switches are used to monitor the status of filters, fans and air flows in the air duct. The product can also intuitively rotate the setting knob to the required pressure value according to the site needs, and ensure the accuracy of the pressure measurement value.
Honeywell Differential pressure switch for air (DPS)
APPLICATION
BENEFITS
Brand name | Honeywell |
Product name | Air Differential Pressure Switch |
Max. operating pressure | 10 kPa |
Pressure connections | two plastic tubes, outside diameter: 6.0 mm |
Switching capacity | 1.5 A, (0.4) /250 Vac |
Protection class | IP 54 |
Mounting lugs | integrated in bottom housing |
Medium/ambient temp | -20...+85 °C |
Storage temperature | -40...+85 °C |
Membrane material | silicone |
Electrical connections | AMP connectors, 6.3 x 0.8, DIN 46244 or screw terminals |
Conduit entry | M20x1.5 |
product delivery
The delivery includes (in the case of individual packages) the following parts:
DPS Differential Pressure Switch
Data Sheet with installation information
DPSA duct kit, consisting of:
Bulk packages available, upon request.
Honeywell Differential pressure switch for air (DPS)
Filter monitor or flow switch for air, non-combustible, non aggressive gases in air conditioning and ventilating installations.
Kind of pressure: overpressure, relative
Pressure connection: plastic connection piece for 5 mm (internal) hose
Electrical connection: AMP connector 6,3x0,8 (DIN 46244) or screw terminals
Protection class: IP54
Sensing element material: ABS + Silicon
Media temp.: -20...85C
Ambient temperature: -20...85C
Switch function/capacity: SPDT switch 240 Vac; 1,5 A (0.4)A
Certificates: CE0085AR0013 according EC Gas Appliance Directive EU/2009/142/EG and DIN EN 1854
Accessories supplied with pressure switch: 2 m silicon hose, 2 connection pieces with mounting screws, 2 self tapping screws for mounting on housing, 3 screw terminals for electrical connection.
Max. pressure: 10kPa
Pressure adjustment range: 40...400Pa
Switching differential: 0.2mbar
DPS2000 500-2500Pa 150Pa
DPS1000 200-1000Pa 100Pa
DPS400 40-400Pa 20Pa
DPS200 20-200Pa 10Pa